Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Bus cable length

It is absolutely necessary to comply with the permissible cable lengths.
1. Please check the compliance with the total cable length in Tab. 1.
The total cable length is defined by the baud rate.
Baud rate [kbps]
20
50
125
250
500
1000
Tab. 1
Total cable length
2. Please check the compliance with the segment cable length in Tab. 2.
The segment cable length is defined by the cable cross−section and the number of bus
devices. Without repeater the segment cable length corresponds to the total cable length.
Bus device
2
5
10
20
32
63
Tab. 2
Segment cable length
EDK82ZAFCC−100 DE/EN/FR 6.0
Max. bus length [m]
3900
1500
610
270
100
9
Cable cross−section
2
0.25 mm
0.5 mm
240 m
430 m
230 m
420 m
230 m
410 m
210 m
390 m
200 m
360 m
170 m
310 m
Electrical installation
2
0.75 mm
650 m
640 m
620 m
580 m
550 m
470 m
l
Bus cable length
2
2
1.0 mm
940 m
920 m
900 m
850 m
800 m
690 m
6