5. MAINTENANCE

Attention: before handling and/or opening the access panels it is compulsory to shut down the power supply
using the general switch located on the front panel. Iif options KWin and\or KWout are installed, then shut down
the corresponding general switches.
Regular maintenance of the HRup unit is essential to guarantee a good operation of the device and a long life
expectancy. The maintenance frequency will depend on the application and on the actual environment conditions
but in a general way the following controls are advised :

5.1. Once the unit operates in normal condition

Replace the starting filters kit by a kit for replacement filters. See Section 1.4 of this booklet.

5.2 Every 3 months

1.
Check for any alarm indicated on the control device. In case of alarm refer to control manual.
2.
Check the state of filter clogging. The control device allows to set a pre-defined 'filter clogging' threshold (refer
to installation manual). If need be replace filters. Filters that are too clogged can generate the following
problems :
Insufficient ventilation
Excessive increase of fan rotation speed, creating excessive sound level
Excessive power consumption (power consumption will increase exponentially to an increase in pressure
drop, for a constant airflow)
A damaged filter allows unfiltered air to enter heat exchanger (risk of clogging) and into ventilated room.
List of replacement filters :
Filters dimensions
Unit type
HRup 450
HRup 800
HRup 1200
HRup 2000
3.
Inspection and cleaning of the inside of the unit:
- Vacuum clean any accumulation of dust in the unit.
- Inspect and gently vacuum clean if need be the heat exchanger. Use brush accessory to protect fins.
- Clean the possible condensation marks and possible accumulations in the drainpan.

5.3 Every 12 months

1.
Check for any alarm indicated on the control device. In case of alarm refer to installation manual.
2.
Check the state of filter clogging. The control device allows to set a pre-defined 'filter clogging' threshold (refer
to installation manual). If need be replace filters. Filters that are too clogged can generate the following
problems :
Insufficient ventilation
Excessive increase of fan rotation speed, creating excessive sound level
Excessive power consumption (power consumption will increase exponentially to an increase in pressure
drop, for a constant airflow)
A damaged filter allows unfiltered air to enter heat exchanger (risk of clogging) and into ventilated room.
See above for list of replacement filters
Filter on
[mm]
supply air
415x200x50
1 x F7
470x287x50
1 x F7
830x287x50
1 x F7
503x370x50
2 x F7
Filter on
Filters kit (supply+exhaust)
exhaust air
1 x G4
1 x F7
1 x M5
1 x F7
1 x M5
1 x F7
2 x M5
2 x F7
33
CID
510014
510071
510089
510072
510090
510073
510091
510054