Schematic Of The T° Sensors Positioning In The Hrup Units; Power Supply To The Fans And The Control Devices; Power Supply For The Electrical Antifreeze Protection Coil Kwin (Option); Power Supply And Connections For The Electrical Post Heating Coil Kwout (Option) - P.LEMMENS HRup 450 TAC5 Manuel D'installation Et De Maintenance

Unité de ventilation double flux avec récupération d'énergie à haut rendement
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.1.2 Schematic of the T° sensors positioning in the HRup unit
To allow easier identification of the temperature sensors 4 different wire colors are used:
T1 : black wire
-
T2 : white wire
-
T3 : blue wire
-
T4 & T5 : green wire
-

3.2 Power supply to the fans and the control devices

All the internal cables (fans, controls, sensors,...) to the main switch are factory pre-wired. All the power supply
wiring that remains is the main power supply to the main switch.
Wiring specifications:
Unit type
Supply Voltage
HRup 450
HRup 800
HRup 1200
HRup 2000
(1) Grounding is compulsory
(2) D type "slow" reaction curves - shutoff power 10.000A - AC3.

3.3 Power supply for the electrical antifreeze protection coil KWin (option)

All the internal cables of the KWin coil to the main switch are factory wired. All that needs to be wired is the main
power supply to the main switch.
Wiring specifications:
Unit type
Supply voltage
HRup 450
HRup 800
3 x 400V + N
HRup 1200
3 x 400V + N
HRup 2000
3 x 400V + N

3.4 Power supply and connections for the electrical post heating coil KWout (option)

All the internal cables of the KWout coil to the main switch are factory wired. All that needs to be wired is the main
power supply to the main switch.
Wiring specifications:
Unit type
Supply voltage
HRup 450
HRup 800
3 x 400V + N
HRup 1200
3 x 400V + N
HRup 2000
3 x 400V + N
Maximum amps
(1)
1 x 230V
1 x 230V
1 x 230V
1 x 230V
14,3 A
KWin heating
capacity
Not available
3 kW
6 kW
6 kW
KWoutn heating
capacity
Non disponible
3 kW
4,5 kW
6 kW
Protection type (2)
3,1 A
D – 10.000A – AC3
5,5 A
D – 10.000A – AC3
7,0 A
D – 10.000A – AC3
D – 10.000A – AC3
Maximum amps
4,3 A
8,7 A
8,7 A
Maximum amps
4,3 A
6,5 A
8,7 A
30
Protection caliber
8A
8A
8A
16A

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Hrup 800 tac5Hrup 1200 tac5Hrup 2000 tac5

Table des Matières