EN
Display
Description
Sum/Win by DIN
Season change from digital inputq
Double set by DIN
Set point change from digital input
Double set
Set point change from digital input (recovery side)
(recovery) by DIN
Recover by DIN
Recovery consent from sequencer digital input
Offset set point
It allows the automatic variation of the machine work Set point according
to a current external signal (4-20mA).
In particular, a value determined by the 4-20mA input is added to or
subtracted from the machine setpoint.
Regulation in both heat and cool mode is as follows:
MAX
MIN
Example:
if the set cool is 12°C and MIN=2 and MAX=4 then the set can range within 14
and 16°C.
if the set cool is 12°C and MIN= -2 and MAX=2 then the set can range within
10 and 14°C.
Shifting set point
It allows the automatic variation of the machine work Set point according
to a current external signal (4-20mA).
In particular, the machine setpoint is not considered in favour of the
value defined by the input 4-20mA.
Regulation in both heat and cool mode is as follows:
MAX
MIN
Example:
if MIN=9 and MAX=14 then the set can range within 9 and 14°C.
4
20
mA
4
20
mA
Section I :: User
Defining the unit activation sequence
If rotation type:USER is set, the following screens are displayed:
Activation sequence defined by the user. Unit 2 will always activate
before unit 1.
Activation sequence defined by the user. Unit 2 will always activate
before unit 1.
Set point menu
The Set point menu allows specifying the sequencer adjustment
temperature.
Press ENTER to access the menu; press the button again to move
between the summer and winter set temperature fields, as well as the
adjustment band.
Menu Clock/Time bands
When you enter Clock/Time
You can set the system time is to enable the time-band operation.
30