Unit Maintenance - SFA SANICONDENS Best Notice D'installation

Masquer les pouces Voir aussi pour SANICONDENS Best:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7e
ALARM
®
SANICONDENS
Best is fitted with a detection system
that can trigger an alarm if the water level rises too high
(audible or visual alarm, 1.5V to 230V), see diagram
1
. Brown wire: shared wire
2
. Black wire: normally off
3
. Blue wire: normally on
To fit the alarm, connect the blue and brown wires
of the alarm to the respective terminals on the
SANICONDENS
®
Best.
OPTIONAL:
if you connect the brown and black wires to the
control relays on your boiler, it will be switched off if the water
level rises too high in the unit.
ATTENTION:
The maximum current admissible for our
detection system is 0.5A
To protect the electrical components in the
SANICONDENS
®
Best, once the alarm has been triggered,
any water continuing to fill the tank comes out through the
overflow outlets in the cover.
7f
EXAMPLE OF AN INSTALLATION OF A SANICONDENS
Best: see fig.
7f
8

UNIT MAINTENANCE

Check the state of the pellets regularly.
Replace the pellets once a year. When replacing the
pellets, also clean the neutraliser drawer.
9
STANDARDS
SANICONDENS
®
Best conforms to the European directive
89/336/CEE on electrical safety.
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
1 0
DISASSEMBLY
If a breakdown occurs, any service on the unit should be
carried out by a qualified engineer. In particular the
replacement of the power cable.
Disconnect the electrical supply before carrying out
work on the unit.
1 1
TROUBLESHOOTING
INSTRUCTIONS RESERVED SOLELY FOR
QUALIFIED PROFESSIONALS
7e
:
Disconnect the electrical supply before carrying out any work.
FAULT DETECTED
• The pump does not start
• The pump does not lift
®
1 2
GUARANTEE
SANICONDENS
parts and labour, subject to correct installation and use of
the unit.
PROBABLE CAUSES
• The pump is not
connected to the power
supply
• Power cut
• Float blocked
• Condensates inlet pipe
blocked
• Neutralisation drawer is
blocked
• Non-return valve blocked
• Discharge pipe blocked
®
Best SFA is guaranteed for 2 years for
ACTION NEEDED
• Plug in the unit.
• Check the mains voltage.
• Clean the SANICONDENS
®
Best tank.
• Clean the SANICONDENS
®
Best inlet pipe.
• Clean the drawer, replace
the pellets
• Clean the valve.
• Clean the discharge pipe.