Note:
2 x Wall bracket
4 x Securing
screws (wood
screws) 5 x 35
Screws 4 x
M5 x 12
Bottom panel
Terminal box
Standfuß
Self-tapping
screws 3.9 x 9.5
Screws 4 x
Sauna
M5 x 12
heater foot
Instructions for the electrician
DIN VDE 0100 and Accident Prevention Regulation BGV A2 must be observed
for connecting the stove and all electrical systems. An external all-pole
disconnecting device with full isolation according to overvoltage category III
must be installed.

Important:

Mains connection leads must be flexible cables with polychlorophene sheaths.
No connection leads are supplied with the stove. All the cables installed inside
the cabin must be suitable for an ambient temperature of at least 140°C. Heat-
resistant silicon cables must be used. The minimum cross-section of the
connection cable and the minimum size of the sauna cabin are shown in the
table (Table 1). Make the electrical connection as shown in the connection
diagram (Page 10). A connection diagram is additionally affixed to the inside of
the duct cover.
Fit the cover after making the electrical connection.
Please note that live cables must not be routed visibly on the internal walls of
the cabin for safety reasons. In prefabricated sauna cabins the wall element
with the air supply opening generally has empty cable conduits or a duct for
routing the cable.
If your cabin does not have any cable routing preparations, we recommend
that you install a connection socket (not supplied) to the outside of the cabin.
Drill a hole in the cabin wall near the cable infeed from the stove and the
connection socket. Thread the cable through the hole to the external
connection socket. All cables must be protected from damage. This can be
achieved using installation ducting/piping or using wooden covers.
Test the insulation resistance
The resistance values between the various conductor terminals and the case
(protective earth) can be measured using an insulation resistance measuring
unit. The total insulation resistance between the conductor terminals and case
(protective earth) must definitely be greater than 1 MOhm.
Ohm values of the stoves
33 – 39 Ω Bio-Kombiofen 9 kW
GB
9