Aiming the flame detector
The flame detector should be aimed toward the center of the
detection zone and have an unobstructed view of the
protected area.
Whenever possible, the flame detector face should be tilted
down at a 45º angle to maximize coverage and prevent
accumulation of dust and dirt.
Do not start an installation unless all conceivable
considerations regarding detection location have been taken
into account.
3.2

Special instructions for safe use

Do not repair or modify the flamepaths of the flame detector.
The unit may be painted or fitted with optional accessories. Some
of these parts are made of a non-metallic material or have a non-
metallic coating which could potentially generate an ignition-
capable level of electrostatic charge under certain extreme
conditions (such as high-pressure steam). Do not damage the
coating and clean the equipment with a damp cloth only to prevent
a build-up of electrostatic charges on the non-conducting
surfaces.
The 3 fastening screws used to secure the cover of the flameproof
compartment have a yield stress of 344 N/mm². Any replacement
fasteners shall have a yield stress of at least this value.
3.3

Preparation for use

Perform the following steps to prepare and install the flame detector.
The installation sequence might vary according to the physical
structure of the site.
1. Install the flame detector:
Mount the tilt mount (see chapter 3.3.1 on page 11).
Attach a conduit connection or cable gland to the flame
detector (see chapter 3.3.2 on page 11).
Attach the flame detector to the tilt mount (see chapter 3.3.3
on page 12).
Wire the flame detector (see chapter 3.3.4 on page 12).
Mount the weather cover (see chapter 3.3.5 on page 12).
Orient the flame detector (see chapter 3.3.6 on page 12).
2. If required, adapt the configuration of the flame detector (see
chapter 3.3.7 on page 13).
3. Power up the flame detector (see chapter 3.3.8 on page 15).
4. Test the flame detector (see chapter 3.3.9 on page 15).
3.3.1
Mounting the tilt mount
► Illustration on the fold-out page (Figure C)
1. Place the tilt mount in its designated location.
2. Secure the tilt mount to the wall with 4 screws and spring washers
1)
(C-1)
.
3.3.2
Attaching either a conduit connection or cable
gland
1. Remove the protective cap from the cable entry.
2. Mount either a ¾"-14 NPT explosion-proof conduit connection or
a M25x1.5 flameproof gland to the cable entry.
1)
screws: either ¼" 20 UNC x ¾" or M6 x 1 x 20 mm
spring washers: either ¼" or M6