GGM AXA1 - Series access control
EN
11.2
Door Settings
Relay Output Delay Time
To set door relay strike time
*
Master Code
0-99 is to set the door relay time 0-99 seconds
Door Open Detection
Door Open Too Long (DOTL) warning. When used with an optional magnetic contact or built-in
magnetic contact of the lock, if the door is opened normally, but not closed after 1 minute, the
inside buzzer will beep automatically to remind people to close the door and continue for 1
minute before switching off automatically.
Door Forced Open warning. When used with an optional magnetic contact or built-in magne-
tic contact of the lock, if the door is forced open, or if the door is opened after 20 seconds
,the inside buzzer and alarm output will both operate. The Alarm Output time is adjustable
between 0-3 minutes with the default being 1 minute.
To disable door open detection. (Factory default)
6
0
#
To enable door open detection
6
1
#
Alarm output time
To set the alarm output time (0-3 minutes)
6
0~3
Factory default is 1 minute
Keypad Lockout & Alarm Output options.
If there are 10 invalid cards or 10 incorrect PIN numbers in a 10 minute period either the key-
pad will lockout for 10 minutes or both the alarm and the inside buzzer will operate for
10 minutes, depending on the option selected below.
Normal status:
7
0
#
No keypad lockout or alarm (factory default)
Keypad Lockout
7
1
#
Alarm and inside buzzer operate
7
2
#
To remove the alarm
To reset the Door Forced Open warning
Read valid card
To reset the Door Open Too Long warning
Close the door or
#
4
0~99
#
*
#
(Factory default setting)
or
Master Code #
Read valid card
or
Master Code #
10