Low DC Warning Return Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Cut-off Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
High DC Recovery Voltage
High DC Cut-off Voltage
No Load Power Consumption
Saving Mode Power Consumption
Table 3 Charge Mode Specifications
Charging Current (UPS)
@ Nominal Input Voltage
Bulk Charging Voltage
Floating Charging Voltage
Overcharge Protection
Charging Algorithm
Charging Curve
30
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 08 17 AA 59 201 05
46.0Vdc
44.8Vdc
42.4Vdc
42.0Vdc
40.8Vdc
38.4Vdc
Default: 30A, Max.: 60A
Battery Voltage, per cell
2.43Vdc (2.35Vdc)
2.25Vdc
T1 = 10* T0, minimum 10mins, maximum 8hrs
Bulk
Absorption
(Constant Current)
(Constant Voltage)
58Vdc
60Vdc
<50W
<15W
56.4Vdc
54Vdc
60Vdc
3-Step
Charging Current, %
Voltage
Current
Maintenance
(Floating)
100%
50%
Time