Fault Reference Code; Warning Indicator - INFOSEC UPS SYSTEM G1 Solar MPPT Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fault Reference Code

Fault Code
01
Fan is locked when inverter is off.
02
Over temperature
03
Battery voltage is too high
Output short circuited or over temperature is detected
05
by internal converter components.
06
Output voltage is too high.
07
Overload time out
08
Bus voltage is too high
09
Bus soft start failed
51
Over current or surge
52
Bus voltage is too low
53
Inverter soft start failed
55
Over DC voltage in AC output
56
Battery connection is open
57
Current sensor failed
58
Output voltage is too low

Warning Indicator

Warning Event
Fan is locked when
inverter is on.
Battery is over-charged
Low battery
Overload
Output power derating
Battery equalization
26
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 08 17 AA 59 201 05
Fault Event
Audible Alarm
Beep three times every
second
Beep once every second
Beep once every second
Beep once every 0.5 second
Beep twice every 3 seconds
Icon on
Icon flashing

Publicité

Chapitres

Table des Matières
loading