DLP180/E
100
80
60
40
20
0
-10
0
10
20
Ambient Temperature (°C)
DLP240/E
100
80
60
40
20
0
-10
0
10
20
Ambient Temperature (°C)

5. Wiring Method

The output load line and input line shall be separated
and twisted to improve noise sensitivity.
Use all lines as thick and short as possible to make
lower impedance.
Noise can be eliminated by attaching a capacitor to
the load terminals.
EMI reduction performance by winding the cable
around
the toroidal ferrice core several times. Use
any appropriate commecially available ferrite core
from local vendor.
For safety and EMI considerations, connect FG
terminal of input connector and mountable FG to
ground terminal of equipment.
Recommened screw torque is 0.49N.m .
Recommened wire type: solid and stranded, AWG
12~20 (wire strip length: 7mm).
85~265VAC
30
40
50
60
85~170VAC
170~265VAC
30
40
50
60
70
6. External Fuse Rating
Refer to the following fuse rating when selecting the external
fuses that are to be used on input line. Surge current flows
when line turns on. Use slow-blow fuse or time-lag type fuse.
Do not use fast-blow fuse. Fuse rating is specified by in-rush
current value at line turn-on. Do not select the fuse according
to input current (rms.) values under the actual load condition.
DLP75/E, DLP75/C2E
DLP100/E, DLP100/C2E
DLP120/E
DLP180/E
DLP240/E
7-1. Power supply mounting on DIN RAIL (TS35 or
equivalent)
(1) Tilt the unit slightly rearwards, fit the unit
over top hat rail.
TDK-Lambda
DLP/E Series
INSTRUCTION MANUAL
5A
5A
5A
5A
6.3A