Electrical connection (continued)
Requirements for complying with the protection
classes:
For IP68/IP69K, all plugs and caps must be properly
connected and the tightening torque of 0.6 Nm must be
observed (see data sheets of connectors and caps).
Grounding
To counteract EMC
interference, the functional
earth connection must be
used.
► Connect the earth terminal
The FE connection between the housing and the
machine must have a low impedance and be as
short as possible.
► Use the grounding strap included in the scope
of delivery.

Cable routing

Cable length
The Ethernet cable may be max. 100 meters long.
The IO-Link single-ended cordset may be max. 20 meters
long.
UL requirements
The power supply has to be an isolated type or SELV type.
Cleaning
Clean the product only with dry cloth or cloth dampened
only with water!
Power Ratings
Power input, nominal
– 130 mA maximum consump-
rated voltage 24 V DC
tion
– 16 A including all output loads
Power output, nominal
– 16 A maximum
rated voltage 24 V DC
Digital input, nominal
– 30 mA max/point (pin)
rated voltage 24 V DC
Digital output, nominal
rated voltage 24 V DC
Class A IO-Link port
– 0,5 A/point (port) Pilot Duty
– 4 A/point (port) Resistive/
General use
– 16 A or less per unit
BNI PNT-538-...,
– 0,5 A/point Pilot Duty
Class B IO-Link port
– Pin 2/5 Fused 1.2 A/point
– Stift 2/3 2 A/point
– 8,8 A or less per unit
www.balluff.com
to the functional earth (FE)
of the machine.
UL requirements (continued)
Cord Sizes
Power In cord assembly:
Listed or R/C (CYJV2/8) cord assembly with threaded
female M12 L-coded connector rated 24 V minimum, 16 A
minimum for all models. Cord Listed S, SJ, SO, ST, SV, or
R/C (AVLV2) marked or specified in UL style page as
suitable for external interconnection rated 300 V minimum,
14 AWG minimum unless marked with maximum load
current and overcurrent protection for the cord in
accordance with table below.
Power Out cord assembly:
Listed or R/C (CYJV2/8) cord assembly with threaded male
M12 L-coded connector rated 24 V minimum, 16 A mini-
mum for all models. Cord Listed S, SJ, SO, ST, SV, or R/C
(AVLV2) marked or specified in UL style page as suitable
for external interconnection rated 300 V minimum, 14
AWG minimum unless marked with maximum load current
and overcurrent protection for the cord in accordance with
table below.
Communication cord assembly:
Listed or R/C (CYJV2) cord assembly with threaded male
or female A, B, or D-coded, as applicable to mate with
item 9, M12 connector rated 24 V minimum, 1 A minimum.
R/C (AVLV2) marked or specified in UL style page as
suitable for external interconnection 28 AWG minimum,
300 V minimum cord.
In/Out cord assembly:
Listed or R/C (CYJV2) cord assembly with threaded male
A-coded M12 connector rated 24 V minimum, 2 A mini-
mum. R/C (AVLV2) marked or specified in UL style page
as suitable for external interconnection Cord rated 300 V
minimum, 24 AWG minimum unless marked with maxi-
mum load current and overcurrent protection for the cord
in accordance with table below.
Cord
14 14 16 18 20 22 24 26 28 30
conductor
size, AWG
Overcurrent
16 12 8 5.6 5
protection
maximum
ampere rating,
Amps
Maximum
16 9
8 5.6 4 2.4 1.6 0.8 0.6 0.4
load, Amps
3
2
1 0.8 0.5
english
4