Status Leds - Balluff BNI PNT-508-055-P067 Notice De Montage

Masquer les pouces Voir aussi pour BNI PNT-508-055-P067:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

BNI PNT-508-055-P067 / BNI PNT-538-055-P067
Network interface
Design and function
FE connection
PROFINET Port 1
Power supply input
Port 0
Port 2
Port 4
Port 6
The Profinet IO-Link master is a decentralized and
configurable gateway that processes and evaluates the
input and output signals of standard sensors and actuators
as well as process data from connected IO-Link devices.
The data is transmitted via an existing fieldbus interface to
a higher-level controller set up by the user for further
processing.
A web server is available on the IO-Link master for
configuration and diagnostics.
Display elements
Port/Pin LEDs
LED 00 – Port-pin 4
LED 01 – Port-pin 2
Port/Pin LEDs Standard-Port
Display
Meaning
Off
State of input or output pin is 0
Yellow
State of input or output pin is 1
Both LEDs
Short circuit of sensor supply between
flashing red
pin 1 and pin 3
Red
Short circuit at output on pin 2/4 against
pin 3
Red
No high signal at diagnostic input
Red
24 V input signal on configured output
(actuator warning)
www.balluff.com
Mounting hole
PROFINET Port 2
Power supply
output
Port 1
Port 3
Port 5
Port 7
Mounting hole
Display elements
Port/Pin-LEDs IO-Link-Port
Display
Meaning
Green
IO-Link connection active
Flashing
No IO-Link connection or incorrect
green
IO-Link device
Green, fast
IO-Link: Preoperate during data storage
flashing
Red, fast
Validation failed / incorrect configuration
flashing
of the IO-Link data length
Red, fast
Data storage failed / incorrect device for
flashing
data storage
Red
IO-Link: Short circuit of pin 4 against
pin 3
Status-LEDs
LED
Display
Meaning
US
Green
Input voltage OK
Red flashing
Input voltage low (< 18 V)
UA
Green
Output voltage OK
Red flashing
Output voltage low (< 18 V)
Red
No output voltage present
(< 11 V)
SF
Off
No error
Red
Watchdog timeout; channel,
general or extended diagnostics
present; system error
Red flashing
Service DCP signal started via
bus
BF
Off
No error
Red
Low speed of physical link; or no
physical link
Red flashing
No data exchange or no
configuration
MS
Green
No error
Blue flashing
Ping command
Blue
Limit exceeded by internal
counter (e.g. operating hours)
Yellow
Sensor supply below 18 V
flashing
Actuator supply below 18 V
No sensor supply 0 V
No actuator supply 0 V
Temperature too low
Temperature too high
Overvoltage
Red
Internal failure
100
Off
Transmission rate: 10 Mbit/s
Yellow
Transmission rate: 100 Mbit/s
XF1/2 Green
Data transfer
flashing
english
2

Publicité