It is possible to reset the Web Server interface parameters (IT500WEB) using the local button.
SW1 button
1. Access credential reset
When it is necessary to reset the credentials to default (default: Username=admin /
Password=WebServer1), proceed as follows:
Set the control unit to maintenance mode (INSTALLER Code -> Maintenance)
Open the control unit
Press and hold the SW1 button for 7 flashes of LED1.
Release the SW1 button, both LEDs will flash to indicate the interface restart.
Check the actual credential deletion.
Close the control unit.
Quit maintenance mode.
WARNING! The control unit is powered, do not touch the plate!
2. Reset factory settings
When it is necessary to reset the interface to factory settings (factory IP address of Web
Server is 192.168.1.100), proceed as follows:
Set the control unit to maintenance mode (INSTALLER Code -> Maintenance)
Open the control unit
Press and hold the SW1 button for 32 flashes of LED1.
Release the SW1 button, both LEDs will flash to indicate the interface restart.
Check the actual parameter deletion.
Close the control unit.
Quit maintenance mode.
WARNING! The control unit is powered, do not touch the plate!
Notes – Web Server Reset