10. Preparation of Electrical Connection by the Customer
Warning!
!
• The power supply (not included in the scope of delivery) must be set up outside of
the wet area, in a separate room.
• Only operate the coin-activated switch with protective extra low voltage (PELV)
24 V DC.
• Secure the electric connection with an earth leakage circuit breaker (RCD) for a
maximum nominal fault current of 30 mA.
Failure to observe can mean risk of death or material damage, e. g. from electric
shock or fire.
☞
Install the system cable (not scope of supply) from the power supply to the the fitting
in a conduit (to be supplied by customer).
☞
Install a conduit Ø
operated switch to the fitting.
11. Assembly Instructions
The coin-activated switch is only suitable for on-wall installation.
☞
Important!
Align the coin-activated switch horizontally.
Failure to observe can cause the coin tester to malfunction.
11.1 Unscrew the frame of the coin-activated switch (PIN-Torx TX-15).
11.2 Mount the frame on the wall horizontally.
11.3 Install the sensor extension cables in such a way that the socket of one cable and
the plug of another cable are next to each other, and then guide them through the
conduit.
11.4 Guide the sensor extension cables through the frame into the coin-activated switch.
11.5 Clip the coin-activated switch on to the top of the tongue and attach.
11.6 Use the screws to fix the coin-activated switch at the bottom.
11.7 Connect the sensor extension lines to the display and the coin slot.
11.8 Open the shower fitting.
☞
The Aquapay fitting must be set to AQUAPAY single shower with the system
software (see instructions 18-05.648, Special Functions chapter).
Remove the checkmark from the Master Mode enable.
= 25 mm (to be supplied by the customer) from the coin-
min