Assembly With Pressure Reducer; Assembly Without Pressure Reducer; Function; Adjust Jet Height - Franke FAID108 2000101103 Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 7
9.

Assembly with pressure reducer

For a flow pressure > 1.2 bar
9.1
Build the water drain.
9.2
Check the height of the water jet.
If the jet height is outside the range of 100 - 300 mm, adjust the jet height
(see
chapter
12.).

10. Assembly without pressure reducer

For a flow pressure 1.0 - 1.2 bar
10.1 To mount the water collection basin, see
10.2 Mount the hose.
10.3 Build the water drain.
10.4 Check the height of the water jet.
If the jet height is outside the range of 100 - 300 mm, adjust the jet height according
to EN 15154 (see

11. Function

11.1 Press the trigger button.
• The water will flow.
11.2 Press the red stop button.
• The water flow will stop.
The fitting is not self-closing, so that the user can hold their eyes open with both
hands!
Depending on the length of the connection hose, the eye shower can also be used
outside the water collection basin.

12. Adjust jet height

chapter
12.).
Work step 9.1
to 9.6.
5

Publicité

Table des Matières
loading

Table des Matières