7-1. Single unit installation

(1) When all walls are within their height limits*.
L3
L1
When the distance behind the unit (L2) needs to be small
When the distance to the right or left (L3) needs to be small
(2) When one or more walls exceed their height limits*.
When the wall(s) at the front and/
or the right/left exceed(s) their
height limits
h3
h1
L3
L1
Add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to L1, L2, and L3 as
shown in the table below.
When the distance behind the unit (L2) needs to be small
When the distance to the right or left (L3) needs to be small
(3) When there are overhead obstacles
≥ 240 (9-1/2)
≥ 45°
≥ 50 (2)
WT08842X01
L2
When the wall at the rear exceeds
its height limit
h2
L2
* Height limit
Front/Right/Left/Rear Same height or lower than the overall height of the unit
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4)
100 (3-15/16)
450 (17-3/4)
300 (11-13/16)
h2
L2
L3
L1
Required minimum distance [mm (in)]
L1 (Front)
450 (17-3/4) + h1
100 (3-15/16) + h2
450 (17-3/4) + h1
300 (11-13/16) + h2
≥ 1000 (39-3/8)
Air outlet guide
(not supplied)
GB-15
L2 (Rear)
L3 (Right/Left)
50 (2)
15 (5/8)
When all walls exceed their height
limits
h3
h1
L3
L3
L1
L2 (Rear)
L3 (Right/Left)
50 (2) + h3
15 (5/8) + h3
[mm (in)]
h2
L2