G
®
PREMASREG
716x
Display readout:
The first line of the display shows the measured
ACTUAL value for volume flow rate, pressure,
contamination degree, or level.
The second line shows the corresponding unit
3
(e.g.: Pa, m
/h, %, cm).
In the third line, the switching status of the relay
(circuit completed/empty) with the corresponding set value
can be read.
If the set value can no longer be represented,
the "limit" designation is issued instead of the value.
If the switching function is deactivated (DIP 3 = OFF),
the third line remains blank empty.
On devices fitted with a valve, the third line is used to
display the time remaining until the next
automatic zero point correction (optional).
Configuring the measuring function:
SET
SET
SELECT
SELECT
min. max.
min. max.
ON
ON
DIP
DIP
Setup button assignment:
1 2 3 4 5 6
1 2 3 4 5 6
SELECT
Pressing for more than 5 seconds =>
switches to setup mode
A short push following thereafter =>
switches to the next input value respectively
12
12
terminates setup mode
11
11
13
13
UP ▲
(arrow pointing up) increases the input value.
Keeping it depressed increases the increment step by step
by which the parameter is increased.
DOWN ▼
(arrow pointing down) decreases the input value.
Pressing for longer increases the increment
step by step by which the parameter is decreased.
Setting the function type
Press the SELECT pushbutton to activate setup mode.
Use the two UP and DOWN pushbuttons to select the desired function
type (formulas for the function types, see page 11).
Complete the entry by pressing the SELECT pushbutton.
After selecting the measuring function, you are automatically guided
through the parameters that must be set (see next page).
14
DOWN
DOWN
AUTO ZERO
AUTO ZERO
UP
UP
OFFSET
OFFSET
min. max.
min. max.
1
1
2
2
3
3
Type 0:
Volume flow rate
Type 1:
Differential pressure
Type 2:
Filter contamination
Type 3:
Liquid level