G
®
PREMASREG
716x
Schematic diagram
Output:
0 -10 V
SET-Setting
switchpoint relay
time Auto Zero (optional)
SET
min. max.
ON
DIP
1 2 3 4 5 6
Plug for
display
NC
12
Normally Closed
COM Common
11
13
NO
Normally Open
Measuring range mode
(Mode selectable)
Unidirectional ( 0 ...+MR ) (default)
Bidirectional (–MR ...+MR )
Measurement signal filtering
(Time interval selectable)
10 s (default)
1 s
®
PREMASREG
716x
Measuring Range
Pressure / Volume Flow
0 ...1000 Pa
k = 3000
94800 m³ ⁄ h
0 ...5000 Pa
k = 3000
212100 m³ ⁄ h
Accessories
ASD-06
Connection set (included in the scope of delivery) consisting of
2 connection nipples (straight) made of ABS, 2 m PVC hose, soft, and 4 tapping screws
ASD-07
2 connection nipples (at 90 degree angle) made of plastic, ABS
WS-03
Weather and sun protection, 200 x 180 x 150 mm, stainless steel V2A (1.4301)
PREMASREG
SELECT
UP
DOWN
Offset correction
ca. ±10 % of final value
OFFSET
min. max.
1
+UB 24V AC/DC
2
Output pressure 0 -10 V in Pa
3
–UB GND (optional for
LCD backlighting)
DIP switch 4 is not assigned!
DIP
Small value suppression (measured values
< 1% of end value (pressure) = 0)
1
OFF
Deactivated (default)
O N
Active
DIP
Service mode
5
(display adjustable)
OFF
Standard (according to configuration) (default)
O N
Service (differential pressure in Pa)
Pressure measuring transducer ⁄ control switches for volume flow,
differential pressure, filter monitoring and liquid level detection, Deluxe
Type ⁄ WG02
®
PREMASREG
7161
P R E M A S R E G 7161- U / W L C D
PREMASREG
®
7165
P R E M A S R E G 716 5 - U / W L C D
®
761x - U ⁄ W
Pushbutton
Zero point setting
AUTO ZERO
Output
0 -10 V
1x Changeover contact
0 -10 V
1x Changeover contact
12
Schematic diagram
PREMASREG
Output:
0 -10 V
-
230V AC
+
24V AC/DC
1 2 3
DIP
Relay
2
(Function adjustable)
OFF
Deactivated (default)
O N
Active (display shows switching point)
DIP
6
OFF
O N
Display
Item No.
■
1302-7161-4161-200
■
1302-7161-4171-200
7100- 0060- 3000-000
7100- 0060- 7000-000
7100-0040-6000-000
Rev. 2019 - V26
®
761x - U ⁄ W
-
PLC
+
PC
DIP
3
OFF
O N
®
PREMASREG
716x
DIP switch 4