Dimensions; Assembly - Helios MBW EC Série Notice De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
EN
CHAPTER 3

DIMENSIONS

CHAPTER 4

ASSEMBLY /

INSTALLATION
+
IMPORTANT NOTE
MegaBox MBW EC.. / MBD EC..
3.0
Dimensions
Fig.5
Dimensions in mm
Type
A
B
MBW EC 225
474
408
276
MBW EC 250
520
446
303
MBW EC 280
569
492
326
MBW EC 315
632
540
369
MBW EC 355
708
600
417
MBD EC 280
569
492
326
MBD EC 315 A
632
540
369
MBD EC 315 B
632
540
369
MBD EC 355 A
708
600
417
MBD EC 355 B
708
600
417
MBD EC 400 A
770
655
450
MBD EC 400 B
770
655
450
4.0
Assembly
m
The MegaBox EC series are designed exclusively for vertical installation on the ground or wall (with bra-
cket) with discharge to the top! (Fig.6/7) (In case of deviating installation conditions the factory should be consulted!).
The series are especially suitable as commercial kitchen extract fans (corresponds to VDI 2052). Please pay
attention to a secure, durable mounting of the unit as well as a free access to the terminal box and the motor-impeller
unit.
Furthermore, prevent vibration transmission to buildings and ducting systems. Therefore, the EC-MegaBox is equipped
with four anti vibration mounts, attached to the two mounting rails and is additionally to be connected via flexible sleeves
FM.. (accessories) to the duct system.
- When installing in ducts make sure that there is a sufficiently long, straight piece of duct ( 2 x duct diameter)
in front and behind the fan as otherwise considerable performance reduction and noise increase will result.
- The MegaBox must be assembled so that service and maintenance can be performed easily and safely. In
this respect, space for door swing-out facility must be considered!
- The installation must be vertical with the condensate drain at the bottom!
Fig.6
Condensate drain
central
C
D
E
F
G
32
232
69
113,5
~635
32
254
89
133,5
~680
32
281
109
142,5
~770
32
310
129
159
~860
33
345
109
176
~955
32
281
109
142,5
~770
32
310
129
159
~860
32
310
129
159
~860
33
345
109
176
~955
33
345
109
176
~955
33
372
129
176
~1025
33
372
129
176,5
~1025
Vertical installation
with wall bracket,
discharge to top
6
H
I
Ø J
Ø K
L
103
200
200
174
211
109
250
250
186,5
223,5
123
280
280
214
251
133,5
355
355
235
272
139
355
355
246
283
123
280
280
214
251
133,5
355
355
235
272
133,5
355
355
235
272
139
355
355
246
283
139
355
355
246
283
144
400
400
256
293
144
400
400
256
293
Fig.7
Vertical installation,
discharge to top
M
N
470
470
620
620
820
620
620
620
820
820
820
820

Publicité