Simplified Installation - Fantech FIT 70E Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation examples (Cont'd)
DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM
to the FURNACE COLD AIR RETURN
SIMPLIFIED INSTALLATION (GOOD)
(RETURN/RETURN METHOD) - OPTION 1
1.
Furnace blower must operate when ventilation from ERV is required. The
furnace should be set to run continuously or interlocked with ERV.
furnace electrical connection on page 19.
2.
A minimum separation of 1m (3`3'') is recommended between the two
direct connections.
3.
In order to prevent exhausting any fresh air, the ERV's exhaust air connection
should be upstream of the ERV's supply air connection when ducting to the
furnace's cold air return.
4.
Due to the difference in pressure between the ERV and the equipment it is
being connected to the ERV's airflow must be balanced on site, using the
procedure found in the section "AIRFLOW BALANCING"
* In the case of a multi-zone system, please contact Fantech customer
service prior to installing any installation type requiring the use of the
furnace interlock"
ERV/Furnace ducting for Simplified Installation - Option 1
* Ductwork layout may
differ depending on model
Outside
Fresh air from
outside
Stale air to
outside
Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost preven-
tion do not include an outdoor air motorized damper. If you are using a simplified instal-
lation, i.e. connecting the ERV supply air duct to a furnace's return air duct, the ERV must
operate continuously. When the ERV is turned off, no warm exhaust air will flow through
the ERV but the furnace's fan will continue to draw in outdoor air directly into the furnace.
If it's cold outside, cold air will be introduced, without re-heating, directly into the furnace.
If the ERV is installed such that the homeowner may turn off the ERV during the winter, we
recommend installing a motorized damper between the ERV's supply air and the furnace's
return air duct that closes when the ERV is not operating. See wiring diagram (figure 1).
1 m (3' 3") min.
Air from inside
Fresh air to
living areas
* Unit air flow should be balanced while ERV is on "Normal" speed and
furnace blower is running.
Suggested installation for:
• When bathroom and kitchen
already have local exhaust
system
• May be suitable for
retrofitting
Benefits: Least expensive
See
installation type
recommended
1 m (3' 3")
min.
recommended
Cold air
return
24 VAC Transformer
24V
120V
COM
ERV Furnace interlock
See page 19.
Figure 1
*Transformer and Damper motor not included
Damper
Motor
NO
7

Publicité

Chapitres

Table des Matières
loading

Table des Matières