Indoor Unit - Mitsubishi Electric CITY MULTI PKFY-P VKM-E Série Manuel D'installation

Masquer les pouces Voir aussi pour CITY MULTI PKFY-P VKM-E Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Installing the refrigerant piping
B
Fig. 4-3
„ PKFY-P·VKM-E
C
Fig. 4-4
8
A
4.3. Refrigerant piping (Fig. 4-3)

Indoor unit

1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil
(available from your local supplier) to the flare sheet surface.
3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover that is attached to the gas pipe and make sure that the
connection join is not visible.
5. Wrap the pipe cover of the unit's liquid pipe and make sure that it covers the
insulation material of the on site liquid pipe.
6. The portion where the insulation material is joined is sealed by taping.
A Site-side refrigerant piping
B Unit side refrigerant piping
4.3.1. Storing in the piping space of the unit (Fig. 4-4)
1. Wrap the supplied felt tape in the range of the refrigerant piping which will be
housed within the piping space of the unit to prevent dripping.
2. Overlap the felt tape at one-half of the tape width.
3. Fasten the end portion of the wrapping with vinyl tape, etc.
A Gas pipe
B
B Liquid pipe
C Indoor/outdoor connection cable
A
D Felt tape 3
D

Publicité

Chapitres

Table des Matières
loading

Table des Matières