U
SE
C
ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME
1) Install upstream of the apparatus a 16A magneto-thermal switch with intervention curve B or C.
2) Connect the power cord supplied with the UPS to the IEC 16A inlet socket.
3) Connect the power cord from the UPS to the mains.
4) Press the main switch on the front panel.
5) After a short time, the UPS comes on, the display lights, a beep sounds and the
The UPS is in stand-by mode: this means that the UPS is in a minimum consumption condition. The
microcontroller is powered and performs its supervision and self-test task; the batteries are charging;
everything is ready for activation of the UPS. There is also a stand-by operating mode when in
battery-powered operation, provided the timer has been activated.
6)
Connect the item(s) of equipment to be powered to the outlets on the rear of the UPS using the cable
supplied or another cable of max. length 10 metres.
WARNING: do not connect equipment that absorbs more than 10A to the IEC 10A outlets. For
equipment items exceeding this level of absorption, use only the IEC 16A socket.
7) Check the machine settings on the display (see the section: Configuration area)
S
WITCHING ON FROM THE MAINS
Press the "ON" button. After it has been pressed, all the icons on the del display light for 1 second
1)
and the UPS sounds a beep.
2)
Switch on the equipment item(s) connected to the UPS.
Only when switching on for the first time: after about 30 sec. have elapsed, check that the UPS is
working properly:
1.
Simulate a black-out by opening the switch placed upstream of the UPS.
2.
The load must continue to be powered, the
be heard every 4 seconds.
3.
When the upstream switch is closed again, the UPS should return to mains-powered operation.
S
WITCHING ON FROM THE BATTERY
1)
Press the main switch on the front panel.
Hold the "ON" button down for at least 5 seconds. All the icons on the display light for 1 second and
2)
the UPS sounds a beep.
3)
Switch on the equipment item(s) connected to the UPS.
S
WITCHING THE
To switch the UPS off, hold down the "STBY" button for at least 1.5 seconds. The UPS returns to stand-by
mode and the
icon starts blinking:
a.
If the mains line is up, to switch the UPS off completely, press the main switch, bringing this
switch back into its original position (raised position).
b.
If the UPS is on battery-powered operation and the timer has not been set, it switches off
completely and automatically after 5 seconds. If on the other hand, the timer is set, to switch the
UPS off, hold the "STBY" button down for at least 5 seconds. If you want the UPS to remain
switched off completely when the mains power returns, then press the main switch (see step a.).
50
UPS
OFF
icon on the display must light, and a beep must
icon blinks.