MSTA: Metering statistics
Attribute Name
Attr. Type
LNName
Data
Common Logical Node Information
Measured values
AvAmps
MV
MaxAmps
MV
MinAmps
MV
AvVolts
MV
MaxVolts
MV
MinVolts
MV
AvVA
MV
MaxVA
MV
MinVA
MV
AvW
MV
MaxW
MV
MinW
MV
AvVAr
MV
MaxVAr
MV
MinVAr
MV
Private Extensions
AvA
WYE
MaxA
WYE
MinA
WYE
AvPPV
DEL
MaxPPV
DEL
MinPPV
DEL
AvPhV
WYE
MaxPhV
WYE
MinPhV
WYE
AvVAPh
WYE
MaxVAPh
WYE
MinVAPh
WYE
AvWPh
WYE
MaxWPh
WYE
MinWPh
WYE
AvVArPh
WYE
MaxVArPh
WYE
MinVArPh
WYE
Unbalanced 4-wire systems only
Unbalanced 3-wire systems only
Single phase or balanced 3-wire systems only
Explanation
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
LN shall inherit all Mandatory Data from Common Logical Node Class
Average current system (single phase measurement only)
Maximum current system (single phase measurement only)
Minimum current system (single phase measurement only)
Average voltage system (single phase measurement only)
Maximum voltage system (single phase measurement only)
Minimum voltage system (single phase measurement only)
Average apparent power
Maximum apparent power
Minimum apparent power
Average real power
Maximum real power
Minimum real power
Average reactive power
Maximum reactive power
Minimum reactive power
Average phase currents (I1, I2, I3, In)
Maximum phase currents (I1, I2, I3, In)
Minimum phase currents (I1, I2, I3, In)
Average phase to phase voltages (V12, V23, V31)
Maximum phase to phase voltages (V12, V23, V31)
Minimum phase to phase voltages (V12, V23, V31)
Average phase to ground voltages (V1N,V2N,V3N,VNE)
Maximum phase to ground voltages (V1N,V2N,V3N,VNE)
Minimum phase to ground voltages (V1N,V2N,V3N,VNE)
Average of apparent power (S1, S2, S3)
Maximum of apparent power (S1, S2, S3)
Minimum of apparent power (S1, S2, S3)
Average of active power (P1, P2, P3)
Maximum of active power (P1, P2, P3)
Minimum of active power (P1, P2, P3)
Average of reactive power (Q1, Q2, Q3)
Maximum of reactive power (Q1, Q2, Q3)
Minimum of reactive power (Q1, Q2, Q3)