■ Power supply specifi cations
Every outdoor unit must have a dedicated power supply.
Main power circuit
◆ Power wiring selection
Power Supply
Model name
Nominal
Phase and
(Standard Model)
Voltage
frequency
MMY-MAP0726FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-MAP0966FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-MAP1206FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-MAP1446FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-MAP1686FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP1926FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP2166FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP2406FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP2646FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP2886FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP3126FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP3366FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP3606FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP3846FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP4086FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP4326FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP4566FT9P-UL
208/230 V
3 ~ 60 Hz
Power Supply
Model name
Nominal
Phase and
(Space Saving Model)
Voltage
frequency
MMY-AP192S6FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP240S6FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP288S6FT9P-UL
208/230 V
3 ~ 60 Hz
MMY-AP336S6FT9P-UL
208/230 V
3 ~ 60 Hz
NOTE
Be sure to follow the above specifications when plugging in.
33-EN
1122001101-2_EN_FR.indb 17
1122001101-2_EN_FR.indb 17
L
L
L
L
L
L
L
L
1
2
3
1
2
3
1
2
Disconnect per NEC
breaker
and local codes.
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Voltage Range
MCA
MOCP
Min.
Max.
(A)
(A)
(V)
(V)
187
253
23.3
30
187
253
34.2
40
187
253
45.4
50
187
253
52.1
60
187
253
66.2
70
187
253
34.2 + 34.2
40 + 40
187
253
45.4 + 34.2
50 + 40
187
253
52.1 + 34.2
60 + 40
187
253
52.1 + 45.4
60 + 50
187
253
52.1 + 52.1
60 + 60
187
253
66.2 + 52.1
70 + 60
187
253
45.4 + 45.4 + 34.2
50 + 50 + 40
187
253
45.4 + 45.4 + 45.4
50 + 50 + 50
187
253
52.1 + 45.4 + 45.4
60 + 50 + 50
187
253
52.1 + 52.1 + 45.4
60 + 60 + 50
187
253
52.1 + 52.1 + 52.1
60 + 60 + 60
187
253
66.2 + 52.1 + 52.1
70 + 60 + 60
Voltage Range
MCA
MOCP
Min.
Max.
(A)
(A)
(V)
(V)
187
253
45.4 + 23.3
50 + 30
187
253
45.4 + 45.4
50 + 50
187
253
66.2 + 45.4
70 + 50
187
253
66.2 + 66.2
70 + 70
– 17 –
L
3
■ Specifi cations for control wiring
Outdoor unit
Header outdoor
*1
U1 U2 S U3 U4 U5 U6 S
Central remote
device (option)
U1 U2
U3 U4
W1
W2
Single port type FS unit
Single port type FS unit
CN02
CN02
U1 U2 A B
CN81
CN81
Indoor unit
Indoor unit
A B
Remote control
CN81
U1 U2 A B
CN81
Indoor unit
Indoor unit
A B
Remote controller
CN81
CN81
U1 U2 A B
Indoor unit
Indoor unit
A B
Remote controller
A B
Single port type FS unit
(Long piping model)
Power supply for
outdoor units
Incorrect
Outdoor unit
Follower outdoor
W1 Control wiring between indoor and outdoor units (Shield wire)
W2 Control wiring between indoor units (Shield wire)
W3 Control wiring between outdoor units (Shield wire)
*1 When perform a central control, connect a relay connector
U1 U2 S U3 U4 U5 U6 S
between [U1, U2] and [U3, U4] terminals in the header unit.
(At shipment from factory : No connection)
*2 Connection of shield wire must be connected
W3
(Connected to all connecting sections in each Indoor unit)
*3 Group control
*2
Single port type FS unit
CN02
U1 U2 A B
U1 U2 A B
U1 U2 A B
CN81
CN81
Indoor unit
Indoor unit
*3
A B
A B
Remote control
Remote control
U1 U2 A B
CN81
U1 U2 A B
CN81
U1 U2 A B
Indoor unit
Indoor unit
A B
A B
A B
Remote controller
Remote controller
Remote controller
A B
A B
A B
A B
Multi port type FS unit (4 port)
CN81
CN81
U1 U2 A B
U1 U2 A B
U1 U2 A B
Indoor unit
Indoor unit
A B
A B
A B
Remote controller
Remote controller
Remote controller
A B
A B
A B
Single port type FS unit
Single port type FS unit
Single port type FS unit
(Long piping model)
(Long piping model)
(Long piping model)
34-EN