SET DATA
4, 7, 10
11
Turn on the power.
1
Push and hold the
SET
,
CL
, and
TEST
at the same time for more than 4 seconds.
The LCD display will start fl ashing.
To set-line (system) address
2
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
3
Push the TIME
/
buttons repeatedly to
set a system address.
(Match the address with the address on the
interface P.C. board of the header outdoor unit in
the same refrigerant line.)
4
SET
Push
button.
(This saves the setting.)
To set-indoor unit address
5
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
6
Push the TIME
/
buttons repeatedly to
set an indoor unit address.
7
Push the
SET
button.
(This saves the setting.)
To set-group address
8
Push the TEMP.
/
buttons
repeatedly to set the CODE No. to
9
Push the TIME
/
buttons repeatedly to
set a group address. If the indoor unit is
individual, set the address to
header unit,
; follower unit,
Individual
: 0000
}
Header unit
: 0001
In case of group
control
Follower unit
: 0002
10
Push the
SET
button.
(This saves the setting.)
45-EN
1122001101-2_EN_FR.indb 23
1122001101-2_EN_FR.indb 23
CODE No.
SET
DATA
SETTING
UNIT No.
R.C.
No.
CODE No.
TEMP.
ON / OFF
3, 6, 9
TIMER SET
TIME
FILTER
RESET TEST
SET CL
1
11
TEST
Push the
button.
The address setting is complete.
buttons
(
fl ashes. The unit can be controlled after
SETTING
has disappeared.)
SETTING
NOTE
1. Do not use address numbers 29 or 30 when setting
system addresses using the remote control.
These 2 address numbers cannot be used on
.
outdoor units and the CODE No. [E04] (Indoor/
outdoor communication trouble) will appear if they
are mistakenly used.
2. If addresses to indoor units are set in 2 or more
refrigerate lines manually by using the remote
control and will control them centrally, set the header
outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface
P.C. boards.
• Turn off DIP switch 2 of SW30 on the interface
P.C. boards of all the header outdoor units
connected to the same central control, except the
.
unit that has the lowest address. (For unifying the
termination of the wiring for the central control of
indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor
unit of each refrigerate line.
• After finishing all the settings above, set the
address of the central control devices. (For the
setting of the central control address, refer to the
installation manuals of the central control
devices.)
.
;
.
– 23 –
■ Using the remote control
to review the address and
position of an indoor unit
How to determine an indoor unit address if
the unit position is known.
This instruction works for indoor units that have
individual, or group control. This must be done while
the units are operating.
CODE No.
UNIT No.
3
°F
No.
1
TEMP.
ON / OFF
TIMER SET
TIME
FILTER
RESET TEST
SET CL
2,4
1
If the unit is "OFF" turn it "ON"
2
Push the left end of the "UNIT LOUVER
" button.
3
Unit number will be indicated on the
control LCD as shown above. The numbers
will disappear after a few seconds. The
numbers indicate the system address
and the unit address for the indoor unit in
question.
4
If 2 or more indoor units are connected to
a group control the address for the next
consecutive unit will appear each time the
left end of the "UNIT LOUVER
button is pushed.
How to determine an indoor unit position if
the unit address is known.
This instruction works for group controlled units only.
This instruction must be done while the units are not
operating.
CODE No.
SET
DATA
SETTING
UNIT No.
R.C.
No.
TEMP.
ON / OFF
TIMER SET
TIME
FILTER
6
RESET TEST
SET CL
2
1
If the unit is "ON" turn it "OFF"
2
Simultaneously push and hold the "VENT
VENT
TEST
" and "TEST
" buttons for more
than 4 seconds.
ON / OFF
.
3
"ALL
" will appear on the control LCD
display. The fans and louvers of all the
indoor units in the control group will be
activated.
4
Push the left end of the "UNIT LOUVER
" button.
5
Each time the left of the button is pushed
the next consecutive indoor unit address
(in the group) will be displayed. While the
address is displayed the fan and louvers
for that indoor unit will operate. For all
other units in the group the fan and louvers
"
will stop.
6
Push the "TEST
TEST
" button to fi nish the
procedure. All the indoor units in the
control group will stop.
3
1
4,5
ON / OFF
.
46-EN