TERMINAL BOARD CONNECTIONS
Terminals Function
1 - 2
POWER SUPPLY
M1
TRANSFORMER
M2
TRANSFORMER
4 - 5 - 6
MOTOR
7 - 8
FLASHING LIGHT
9 - 10
STOP
9 - 11
PEDESTRIAN
9 - 12
OPEN/CLOSE
13 - 14
OPEN
13 - 15
CLOSE
13 - 16
PHOTOCELL
FIXED SAFETY
17 - 18
EDGE
19 - 20
not
connected;
21 - 22
2
RADIO CH
nd
Description
(Power supply) POWER input 230Vac, 50Hz, single-phase;
transformer primary connector [2 white wires (230V) + 2 red
wires (80V)];
transformer secondary connector [(2 black wires
blue wires (15V)];
(Motor) MOTOR output single-phase 230Vac, 600 W, com-
mon=4, opening phase=5, closing phase=6, connect the ca-
pacitor between terminals 5 and 6;
(Flashing light) FLASHING LIGHT output 230 Vac 50 W
max. The signal is already modulated for direct use. Flashing
frequency during closing is
(Stop) STOP button input (normally closed contact); this
stops the automatic system. At the next command, the oppo-
site operation to the previous one is performed (common=9);
(Pedestrian) PEDESTRIAN button input (normally open con-
tact); partially opens the automatic system (by about 1 m) to
allow pedestrians to pass by (common=9);
(Open/Close) OPEN/CLOSE button input (contact normally
open); for operating information see dip switch 2 - 4 and 10
functions (common=9);
(Open) OPEN button input (contact normally open); for op-
erating information see dip switch 2 and 10 functions (com-
mon=13);
(Close) CLOSE button input (contact normally open); for op-
erating information see dip switch 2 and 10 functions (com-
mon=13);
input for PHOTOCELLS OR SAFETY DEVICES
(Photocell)
active during closure (Normally Closed contact); They stop
the gate during closing and totally reopen it; they temporarily
stop the gate during opening in order to allow the obstacle
to be removed (if dip switch n° 3 set to ON), (13= Common).
If there is more than one safety device, connect all the NC
contacts IN SERIES.
(Fixed safety edge)
sitive edge or fixed safety edge);
Works only when the gate is opening; temporarily stops the
gate and partially closes it by about 20 cm in order to allow
the obstacle to be removed. (17=Common);
Note: if a resistive sensitive edge is connected, short
jumper J1;
If a fixed edge with NC contact is connected, leave jump-
er J1 open;
(2nd radio channel)
eration depends on dip-switches nos. 7 - 8) to be used for
opening/closing another gate, for controlling garden lights or
for the "ZONE LIGHTING" function;
Warning: to connect other devices to the 2nd Radio
Channel (area lighting, pumps, etc.), use an additional
auxiliary relay.
D705M
double. 7= 230 Vac, 8= 0 V
SENSITIVE EDGE input (resistive sen-
2nd RADIO CHANNEL output (its op-
(24V)
+ 2
15