Plug and socket system 125 A, GHG 525
2

Safety instructions

Target group:
For skilled electricians and suitable
qualified, instructed personnel in
accordance with national legislation,
including the relevant standards.
The GHG 525 plugs and sockets are not
suitable for explosion hazardous areas.
Modifications to the plugs and sockets or
changes of their design are not permitted.
They shall be used for their intended
purpose and in perfect and clean condition.
For replacement and repair only genuine
CEAG/Eaton spare parts shall be used.
Repairs that affect the explosion protection,
may only be carried out by CEAG/Eaton or a
qualified electrician in compliance with the
respective national regulations.
Prior to taking the plugs and sockets into
operation, they will have to be checked in
acc. with the instruction as per section 6.
The sockets may only be used in undam­
aged condition. Before the initial operation,
any foreign matter will have to be removed
from the the plugs and sockets.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
3

Conformity with standards

The apparatus are conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
4

Field of application

The plugs and sockets GHG 525, acc to.
IEC/EN 60309 are suitable for use in heavy
industrial areas! The enclosure materials
employed, including the exterior metal parts,
are made of high-quality materials which
ensure a corrosion protection and resistance
to chemical substances corresponding to the
requirements in a "normal industrial atmos-
phere":
- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L.
In case of use in an extremely aggressive
atmosphere, the additional data on the
employed plastic materials'resistance
against chemicals will have to be taken
from the data sheet GHG 902 4001 P0001.
5
Use/Properties
The GHG 525 plugs and sockets are used for
the power supply of local controls with varying
locations, as well as of electrical installations,
mobile machinery and driving gear in industrial
areas. Acc. to IEC they are used up to max.
125A (see page 7 , Technical data).
The plugs and sockets can generally be used
for the voltage range laid down in IEC/EN 60309
(e.g. U
400V that corresponds to the voltage
N
range 380-415V).
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
Fig. 1: In order to activate the sockets, first
the bayonet ring item 2 is to be screwed off
the socket item 1 and to be folded open.
Fig. 2: After pushing the plug into the socket,
the bayonet ring of the plug item 2 is screwed
to its stop onto the socket in order to establish
IP 66 protection category.
For operating the 4­pole wall socket (with
interlocking switch) proceed as follows:
Fig. 1 + fig. 2: As described above.
Fig. 3: The switch item 3 is switched on,
thereby locking the plug in the socket.
Proceed in inverse order to switch off and pull
the plug from the wall socket with switch.
After having removed the plug from the socket,
close the latter with the folding cover and
secure it with the bayonet ring in order to estab-
lish IP 66 type of protection.
The plug can be pushed into the socket and
pulled out of it only whilst the wall socket
with switch is switched off.
The user alone is responsible for the
appropriate use of this plug and socket
system.
After a short in the circuit, the operative ness
has to be checked.
The data as per point 3 and 4 will have to be
taken into account with the use.
Applications other than described are not
permitted without CEAG/Eaton's prior
written consent.
For the operation, the instructions stated in
section 7 of the operating instructions will
have to be observed.
In the open air, the plugs must be kept with the
plug opening (pin side) pointing down-wards or
be closed with protective plug caps available as
an optional extra (see general catalogue).