2
Safety instructions
The GHG 619 wall sockets
are not suitable for Zone 0 and
Zone 20 hazardous areas.
The temperature class and
explosion group marked on the apparatus
shall be observed.
The electrical connection of the device
may only be carried out by skilled staff
IEC/EN 60079-14.
Modifications to the plugs and sockets or
changes of their design are not permitted.
They shall be used for their intended pur-
pose and in perfect and clean condition.
The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and tem-
perature to be considered from the user.
To ensure adherence to the temperature
class stated on the type label of the ap-
paratus, the permissible ambient tempera-
ture, the rated terminal cross section and
the self heating of the apparatus that is
mainly due to the power dissipation shall
be taken into account (test criterion for the
self heating is an overload of 10%).
For replacement and repair only genuine
COOPER CROUSE-HINDS spare parts shall
be used.
Repairs that affect the explosion protec-
tion, may only be carried out by COOPER
CROUSE-HINDS or a qualified electrician
in compliance with the respective national
regulations.
Prior to taking the plugs and sockets into
operation, they will have to be checked
in accordance with the instruction as per
section 6.
The interlocking switch of the socket is
mechanically secured and cannot be con-
nected without plug.
The sockets may only be used with the
associated COOPER CROUSE-HINDS plugs
in undamaged condition.
The plugs GHG 532 can further on be
inserted with the sockets of the series
GHG 532.
Before the initial operation, any foreign
matter will have to be removed from the
the plugs and sockets.
Observe the national safety rules and regu-
lations for prevention of accidents as well
as the safety instructions included in these
operating instructions and set in italics the
same as this text!
6
Explosion protected plug and socket system 32 A, GHG 619
1
Technical data
ATEX type examination certificate:
Marking acc. to 94/9/EG and standard:
EN 60079-0
IECEx type examination certificate:
Category of application:
IEC60079-0
Rated voltage:
GHG 619
(max. 230 V between L1 and N)
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3:
Perm. ambient temperature:
Special versions permit deviating temperatures.
Perm. storage temperature in original packing:
Protection category acc. to IEC/EN 60529
with closed and secured hinged cover as well
as combinations properly plugged together
* Attention! When the Plugs GHG 532 is
insert with sockets of the series GHG 619,
the "IP" protection category of the combina-
tion is reduced to the minimum protection
category "IP 54".
Insulation class acc. to IEC/EN 61140:
Cable entry:
Wall socket
suitable cables and test torques of the
pressure srew
seel 1+2
min.
1
2
max.
seel 2
min.
1
2
max.
Test torque for screw in thread cable entry
(1)
The maximum clamping area for cables with the seal combination 1+2 can vary according to the type
of cable used.
(2)
When selecting the seal rubber, ensure that the pressure screw can be tightened when carrying out any
future maintenance work on the cable entry.
Supply terminal:
Wall socket, flange socket
Test torques:
Cap nut of the entry
for min. cable Ø in Nm
for max. cable Ø in Nm
Cover screws
Terminals
Self-cutting screws size 4
Self-cutting screws size 5
Weight:
Wall socket
5-pole
Auxiliary contact, rated voltage:
Auxiliary contact, rated current:
EATON's Crouse-Hinds Business
B 99 ATEX 1044
II 2 G Ex de [ia] IIC T5 / T6
II 2 D Ex tD A21 IP66 T80 °C*
IECEx BKI 06.0007
Ex de [ia] IIC T5 / T6
Ex tD A21 IP66 T80 °C*
to 415 V, 50/60 Hz
max. 32 A
GHG 619
max. 35 A
max. 50 A gL
690 V/32 A
-20° C to +40° C (catalogue version)
-20° C to +40° C
IP 66 (catalogue version) *
I - is complied with by the devices
(catalogue version)
2 x M40:
1x Ø 19 - 28 mm + 1x screwed blanking plug
Ø
19.0
(1)(2)
22.0
22.0
(2)
28.0
7 .5 Nm
Cross section
2 x 4.0 - 10 mm²
3.3 Nm
6.7 Nm
2.5 Nm
2.5 Nm
2.0 Nm
3.0 Nm
(catalogue version)
GHG 619
approx. 3.00 kg
250 V AC
AC / 5 A
E
GHG 619 / GHG 532
35 A
40 A gL
Nm
3.3
5.5
3.3
6.7
Stripped wire length
12 mm
DC / 0.03 A