Cable Size
Heatless DX Models
Recommended cable rating for 240V/1ph/ 50Hz supply is 1.5mm
Heat Regenerative DH Models
Important Notice:
Due consideration should be given to voltage drop when sizing electrical supply cables.
Voltage at the dryer must be between +5% to -10%. Wiring must be in accordance with the latest edition IEE wiring
regulations or equivalent local standards.
MODEL
DH 40
DH 80
DH 120
DH 160
DH 190
F) Electrical Connection Heatless DX Models
Open control shroud and identify location of Electric Cam Timer.
Feed supply cable through cut outs provided in instrumentation shroud support bracket, allowing adequate cable
for connection.
Remove electric cam timer cover and feed cable through gland in the side of the Electric Cam Timer enclosure.
Connect 240V/1 ph/50hz supply to the terminal blocks provided.
For other voltages, refer to diagram printed on the inside of the enclosure.
FULL LOAD AMPS
A
7.2
14.4
21.6
28.8
36.0
POWER CONSUMPTION - HEAT REGENERATIVE
HEATLESS ELECTRICAL CAM TIMER ENCLOSURE
2
.
POWER CONSUMPTION
KWh AVERAGE
1.1
2.2
3.3
4.4
5.5
26
COLUMNS
2
4
6
8
10