Operation Range; Main Components; Selection Of Location; Inspecting And Handling The Unit - Daikin EWWQ014KBW1N Manuel D'installation

Masquer les pouces Voir aussi pour EWWQ014KBW1N:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 16
O
PERATION RANGE
EWWQ014~033
LWC
60
55
50
45
40
30
20
a
a
a
b
b
b
ZH
ZH
ZH
10
ZL
ZL
ZL
0
–5
1.5
1.5 1.5
5
32
–10
0
10
20
LWC
Leaving water temperature condenser
LWE
Leaving water temperature evaporator
a
Glycol
b
Water
Continuous operation range
M
AIN COMPONENTS
(refer to the outlook diagram supplied
with the unit)
1
Compressor
2
Evaporator
3
Condenser
4
Switchbox
5
Chilled water in
6
Chilled water out
7
Condenser water out
8
Condenser water in
9
Evaporator entering water temperature sensor
10 Freeze up sensor
11 Condenser entering water temperature sensor
12 Digital display controller
13 Power supply intake
14 Ball valve (field installed)
15 Water filter (field installed)
16 Air purge valve (field installed)
17 T-joint for air purge (field installed)
18 flowswitch (with T-joint) (field installed)
19 Main switch
S
ELECTION OF LOCATION
The units are designed for indoor installation and should be installed
in a location that meets the following requirements:
1
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
2
The space around the unit is adequate for servicing.
3
There is no danger of fire due to leakage of inflammable gas.
4
Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone.
5
Ensure that water cannot cause any damage to the location in
case it drips out of the unit.
The equipment is not intended for use in a potentially explosive
atmosphere.
I
NSPECTING AND HANDLING THE UNIT
At delivery, the unit should be checked and any damage should be
reported immediately to the carrier claims agent.
Installation manual
2
EWWQ049~064
LWC
60
55
50
45
40
30
20
a
a
a
b
b
b
ZH
ZH
ZH
10
ZL
ZL
ZL
0
–5
–2
-2 -2
5
32
–10
0
10
20
U
NPACKING AND PLACING THE UNIT
1
Cut the straps and remove the cardboard box from the unit.
2
Cut the straps and remove the cardboard box with waterpiping
from the pallet.
3
Remove the four screws fixing the unit to the pallet.
4
Level the unit in both directions.
5
Use four anchor bolts with M8 thread to fix the unit in concrete
(directly or using the floor standing supports).
6
Remove the service front plate.
I
MPORTANT INFORMATION REGARDING THE
REFRIGERANT USED
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type:
R410A
(1)
GWP
value:
2090
(1)
GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate.
C
HECKING THE WATER CIRCUIT
The units are equipped with water inlets and water outlets for connec-
tion to a chilled water circuit and to a hot water circuit. These circuits
must be provided by a licensed technician and must comply with all
relevant European and national regulations.
The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.
Before continuing the installation of the unit, check the following
points:
Additional components not delivered with the unit
1
A circulation pump must be provided in such a way that it dis-
charges the water directly into the heat exchanger.
2
Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down.
3
Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.
EWWQ014~064KBW1N
Packaged water-cooled water chiller
D-EIMHP00901-18EU

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ewwq064kbw1nEwwq025kbw1nEwwq033kbw1nEwwq049kbw1n

Table des Matières