RHOSS ELECTA Série Mode D'emploi page 302

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

EN
Menù
Par
Label
Description
label
Frost protection, mode:
On: Frost protection from "USER INTERFACE". The protection
241
AFEn
Off: Frost protection from PdC controller (PCB DISPLAY, switch 1 to
ON)
242 AFSU
protection starts up (Pump 1 on)
243
AFSA
protection starts up (Pump 1 on)
AFr
Water temperature (par. 109 /111) below this the second level of
244
AF2U
frost protection starts up (the water heats up from PcD and/or addi-
tional generator)
Frost protection, differential: The differential applied to the above
245
diFA
temperatures (AFSA,AFSU,AF2U). Exceeding this, the respective
protection levels are disabled
The water temperature, at the outlet of the heat pump, requested to
246
AFtU
trigger the second frost protection level
NOTE: If par. 110 = 3 the controls on the water temperature are not carried out on par. 111.
inside the PdC must be disabled (PCB DISPLAY, switch 1 on OFF)
Enclosed documents
302
U.m.
Range
max Default t
min
-
Off
On
Off
°C
2
-10
2
°C
1
-10
1
°C
1
-15
-1
°C
1
15
5
°C
5
30
5
Correct
Address
On
16443
1644
16445
16384
16446
16447

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Thaity 105-110-116

Table des Matières