Dimensions in mm
X = fixing dimensions
10 A 3-pole
25 A 3-pole
25 A 6-pole
14
Switches, GHG 981,
industrial design up to 250 A, 3 and 6-pole
1�2
Safety switch 10 A; GHG 981 001
Rated voltage:
Rated current:
Perm� short circuit back-up fuse:
Switching capacity AC 3:
Cable entries (standard version):
suitable cables and test torques of the pressure screw
Cabel entry:
Seal 1+2+3
1 2
3
(Ø mm / Nm)
Seal 1+2
1 2
3
(Ø mm / Nm)
Seal 1
1 2
3
(Ø mm / Nm)
Pressure screw (Nm)
(1)
The tests of clamping ranges and torque values were performed with metal mandrel� The clamping range can
vary by using cables with different manufacturing tolerances and material properties� Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry�
Terminals:
Test torques:
Terminals main / auxiliary contact:
Weight (standard version):
1�3
Safety switch 25 A; GHG 981 0037 - 3-pole; GHG 981 0038 - 6-pole
Rated voltage:
Rated current:
Perm� short circuit back-up fuse:
Switching capacity AC 3:
Cable entries (standard version):
suitable cables and test torques of the pressure screw
Cabel entry:
Seal 1+2+3
1 2
3
(Ø mm / Nm)
Seal 1+2
1 2
3
(Ø mm / Nm)
Seal 1
1 2
3
(Ø mm / Nm)
Pressure screw (Nm)
(1)
The tests of clamping ranges and torque values were performed with metal mandrel� The clamping range can
vary by using cables with different manufacturing tolerances and material properties� Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry�
Terminals:
Test torque terminals:
Weight (standard version):
500 V, 50/60 Hz
10 A
up to U
400 V
N
20 A/gL
10 A
3-pole version
1 x M20 + 2 x M25
M20
min�
5�5 /1�5
max� (1)
7 �0 / 1�0
min�
7�0 / 1�5
max� (1)
9�0 / 1�4
min�
9�5 / 1�0
max� (1)
13�0 / 1�7
2�7
2 x 1�5 - 2�5 mm²
2�50 Nm
3-pole - approx� 0�56 kg
690 V, 50/60 Hz
25 A
up to U
400 V
N
35 A/gL
20A
3-pole version
2 x M32 + 1 x M25
M25
min�
8�0 / 1�5
max� (1)
10�0 / 2�0
min�
10�0 / 2�3
max� (1)
13�0 / 2�6
min�
13�5 / 1�3
max� (1)
17 �5 / 2�3
3�0
2 x 1�5 - 4�0 mm²
2�50 Nm
3-pole - approx� 1�48 kg
GB
up to U
500 V
N
16 A/gL
10 A
M25
8�0 / 1�5
10�0 / 2�0
10�0 / 2�3
13�0 / 2�6
13�5 / 1�3
17 �5 / 2�3
3�0
up to U
500 V
up to U
690 V
N
N
–-
25 A/gL
16A
10A
6-pole version
4 x M32 + 1 x M25
M32
14�0 / 3�0
17�0 / 4�0
17�5 / 1�5
21�0 / 1�3
5�0
6-pole - approx� 2�43 kg