Appendix 1: Wattmeter
4.
Accepting this gains access to the password
configuration screen CNG PASS. It is recommended
that you do not modify the value and move the
joystick right to move to the next screen.
5.
APPLICAT application type Screen. Select the
application type H in this screen. To do this press
the joystick once. At the bottom of the display PRG
appears, indicating that it is possible to modify the
value. Move the joystick in any of the 4 directions
until TYP.H appears. Press the joystick once to
accept.
6.
Move to the SYS system type selection screen
using the joystick. Press the joystick once (the PRG
indication will appear on the bottom of the display).
Move the joystick in any of the 4 directions until 1P
(in single-phase installations) or 3P.N (in three-phase
installations) is reached. Press the joystick once to
accept.
7.
In the case of the A65+ wattmeter, move to the
transformation ratio selection screen CT RATIO (from
1.0 to 60.00 k). For example, if the primary current
of the transformer is 3000 A and the secondary
current is 5 A, the transformation ratio is 600
8.
Move to the ADDRESS node number screen
using the joystick. Press the joystick once (the PRG
indication will appear on the bottom of the display).
Move the joystick in any of the 4 directions until
the number 1 is selected. Press the joystick once to
accept.
Accepting this gains access to the BAUD RATE
configuration screen. Press the joystick again (the
PRG indication will appear on the bottom of the
display). Move the joystick in any of the 4 directions
to select 9600 bps. Press the joystick once to
accept.
AAX2002IKH06_A - Installation manual
CnG PASS
0
Applicat
typ.H
PRG
SYS
1p
PRG
SYS
3p.n
PRG
CT RATIO
600
PRG
ADDRESS
1
PRG
BAUD RATE
9600
PRG
Ingeteam
English - 41