Connection Details
(Plug viewed from top)
4 - 20 mA
4
5
1
Pins
1 = +VS
2 = 4 -20 mA out
3 = Frequency ground
4 = O/C frequency pulse out
5 = N/C
N.B. N/C = Do not connect
Connecting cable (5m)
Extension cable (5m)
Connector (M12x1 5 pin)
C2000 mA cable
C2000 TTL cable
HPM6000 mA cable
NB. See manual for precise connection details.
l The flow meter body should be grounded.
l Shielded cables are recommended.
3
l The housing of the transducer is grounded and the cable
shield should connect to this case. Over short distances
the cable shield should be grounded at the receiving end
2
but over longer distances and problematic installations
the shield can be left open circuit or grounded via a
capacitor (typically 100nf).
NB. Ground loop currents can cause inaccurate and erratic
readings.
FT10228-05
FT10229-05
FT9880
FT10951-05
FT10949-05
FT10950-05
Electrical Connections
5