Trumpf TruConvert AC 3025, TruConvert System Control Manuel Opérateur page 71

Onduleur bidirectionnel
Masquer les pouces Voir aussi pour TruConvert AC 3025, TruConvert System Control:
Table des Matières

Publicité

Addr
Description
4005
Precharge DC link confi-
guration:
0 = device waits for exter-
nal precharge of DC link
1 = device precharges
external DC link to neces-
sary start-up voltage
2 = behaviour similar to
1 with additional support
of DC submodules
(necessary for island ope-
ration)
4006
Sets reference frame con-
vention (0 = producer
reference frame; 1 = con-
sumer reference frame)
4007
Specifies the slave that
will be addressed (0 =
broadcast / same values
for all slaves)
4008
Error handling policy for
systems with multiple sla-
ves: 0 = relaxed (System
keeps running even if
some slaves are in error
state.); 1 = strict (System
shuts down as soon as
one component is in
error state.)
4009
Grid type:
0 = grid-tied, 400V, 50Hz
1 = grid-tied, 480V, 60Hz
2 = island mode, 400V,
50Hz
3 = island mode, 480V,
60Hz
4 = grid-tied, 380V, 60Hz
4010
Specifies the subslave
that will be addressed (0
= broadcast / same
values for all subslaves)
4011
Use the modbus slave ID
for addressing
A67-0141-00.BKfr-0
01-07
Unit
Res
Default
olu-
tion
-
1.0
1
-
1.0
0
-
1.0
0
-
1.0
0
-
1.0
0
-
1.0
0
-
1.0
0
2021-03-03
Min
Max
Dat
Typ
atyp
e
e
0
2
UIN
Regi
T16
ster
0
1
UIN
Regi
T16
ster
0
16
UIN
Regi
T16
ster
UIN
Regi
T16
ster
0
1
UIN
Regi
T16
ster
0
16
UIN
Regi
T16
ster
0
1
UIN
Coil
T16
Manipulation
Len
FCr
FCw
gth
1
03
06
1
03
06
1
03
06
1
03
06
1
03
06
1
03
06
1
01
05
65