350-41930
2.17. Manual dimming
With the IR remote control, it is possible to increase and dim the luminaires in all zones simultaneously or in individual zones separately. To increase the light
level, press the 'Dim +' button. Press the 'Dim –' button to reduce the light level. If you have not selected a zone beforehand, the light level will be simultaneously
increased/reduced in all lighting zones. The increase/reduction in the light level will begin when the button is pressed once and will stop when the button is
pressed a second time. The dimming time depends on the actuator.
2.18. Switching the lighting on and off
With the IR remote control, it is possible to switch the luminaires on and off in all zones simultaneously or in individual zones separately. To switch the lighting
on, press 'On'. Press 'Off' to switch the lighting off. If you have not selected a zone beforehand, the light level will be switched on or off in all lighting zones
simultaneously.
3. LED STATUS
LED
The blue LED flashes 2 seconds on and 2
seconds off
The red LED flashes 2 seconds on and 2
seconds off
The red LED lights up continuously
The red LED lights up for 0.5 seconds if
movement in sector A is detected
The green LED lights up for 0.5 seconds if
movement in sector B is detected
The blue LED lights up for 0.5 seconds if
movement in sector B is detected
The green LED flashes once
The red LED will flash a few times (0.2
seconds on and 0.2 seconds off)
The blue LED will flash a few times (0.2
seconds on and 0.2 seconds off)
The green LED will flash four times (0.3
seconds on and 0.3 seconds off)
The green LED will flash twice (0.3 seconds
on and 0.3 seconds off)
The red LED lights up for 0.3 seconds.
The red LED flashes twice
The red LED flashes (2 seconds on and 3
seconds off)
20
Status
Meaning
Connected but not yet
The electricity is connected but the detector is not yet configured.
configured.
Initialisation
After connection to the mains, it takes around 60 seconds until the detector is
ready for use.
KNX programming mode
The address of the detector can now be addressed in the ETS software. The LED
goes out when the configuration is complete.
Walking test sector A
The red LED will flash when movement is detected in sector A.
Walking test sector B
The green LED will flash when movement is detected in sector B.
Walking test sector C
The blue LED will flash when movement is detected in sector C.
IR remote control
Each time the detector receives a correct signal from the IR remote control, the
detector will acknowledge this by lighting up the green LED for 0.3 seconds.
Dim+
The light is increased with the remote control The LED will flash the same amount
of times as the number of steps by which the actual value deviates from the value
which was configured with the ETS software.
Dim-
The light is dimmed with the remote control The LED will flash the same amount
of times as the number of steps by which the actual value deviates from the value
which was configured with the ETS software.
Unlocked ('Unlock')
After flashing four times, the detector will be unlocked and it can then be configured
with the IR remote control.
Locked ('Lock')
After flashing twice, the detector will be locked and the modified settings will be saved.
Function denied
The function you are trying to select can only be performed if the detector is
unlocked. Unlock the detector and try again.
Error message: range
The entered configuration falls outside of the range. This applies both for time
settings and light intensity (lux).
Calibration
The red LED flashes for 2 minutes to indicate that the device is being calibrated.
EN