BCS Q40BBAA-PSICFHC-...
Capacitive Proximity Switches
6
IO-Link Functions (continued)
6.1.8
Physical Output Delay
To suppress short switch-on pulses, the switching signal
activation can be delayed using the On parameter. This
means the output only turns on when an object has been
detected for the configured time. Correspondingly the Off
parameter can be used to affect turn-off.
– The parameter On and Off can be combined.
– These settings have no effect on the IO-Link
process signal.
6.1.9
Physical Output Type
If no master is connected to IO-Link sensors, they
automatically use SIO mode, i.e. the sensor functions as
with a conventional switching final stage. Using this
parameter, the switching final stage can be configured as
PNP, NPN or push-pull.
For changing switching function (NO / NC) see
Section 6.1.6 Switch Point Mode.
6.2
Process data
6.2.1
Input data structure
Byte 1
7
6
5
6.2.2
Input data contents
Name
Data type
PDV1
UINT12
BDC1
Bool
10
english
4
3
2
1
PDV1
← Send Direction
Bit offset
Bit length
4
12
0
1
Byte 0
0
7
6
5
Value range
Description
0...4095
Current sensor value in digits
TRUE = active
Switching state
FALSE = inactive
4
3
2
1
'0'
'0'
'0'
BDC1
0