Motion Detection Sensitivity

Using the Trimpot - HBP-111/112
1. Enter Test Mode by holding push button for approximately 3 seconds. While in test mode, the time delay trimpot functions as a
sensitivity adjustment.
2. Using a screwdriver or fingernail, adjust the time delay trimpot on the sensor to change the sensitivity as follows:
• Low Sensitivity - 5min or 10min position
• Medium Sensitivity - 15min or 20min position
• Maximum Sensitivity - 30min position
3. Exit test mode by pressing and holding push button for approximately 3 seconds.
• For the HBP-111 – If the time delay was originally set manually, using the trimpot,
then you must move the trimpot back to its original setting after exiting test mode, or else the time delay will change to the
present trimpot setting. But if the time delay was originally set using the FSIR-100, then the time delay will automatically revert to
the set amount and will ignore the trimpot setting.
• For the HBP-112 – You must move the trimpot back to its original setting after exiting test mode, or else the time delay will
change to the present trimpot setting.
NOTE: When you exit test mode, adjusting the trimpot will no longer change the sensitivity.
Using the FSIR Remote - HBP-111 only
1. Aim the remote at the sensor.
2. Select New Settings and Sensitivity.
3. Choose from the option of "Min", "Med", or "Max".
4. Select Send.
NOTE: Any adjustments made will override any previous settings whether manually made on the sensor or through the FSIR-100.
Light Level Hold-Off
The Light Level feature holds lights off upon initial occupancy if adequate ambient light exists. It will not turn the lights off if they are on. If
the ambient light level is lower than the factory preset light level or manually adjusted set point, the loads will trigger on once occupancy
is detected. The default setting is for maximum, meaning that even the brightest ambient light will not hold the lights off. When the light
level is set it is written to memory so that in the event of power failure the setting is not lost.
• Avoid mounting in location where adjacent fixtures contribute to the photocell measurement.
• Adjust during daylight hours when ambient light is at the desired level.
Setting Light Level Hold-Off
If desired, set the light level using the steps below. The light level values referenced are approximate and reference 4000K CCT.
Variations in color temperature may affect the actual levels the sensor sees. It is recommended that light level hold off be set up in the
morning for best results.
Trimpot
1. Use screwdriver or fingernail to adjust the trimpot on the sensor housing to desired photocell setting.
2. Use analog wheel with hashmarks (1-300fc).
FSIR Remote
1. Aim the remote at the IR lens on the sensor.
2. Select Adjust Photocell Setting.
3. Choose from the range of 1fc - 300fc with 1 fc increments.
4. Select Send.
NOTE: Any adjustments made will override any previous settings whether manually made on the sensor or through the FSIR-100.

Push Button Functions

The following functions are available by pressing the Push Button per the instructions, below.
Manual Mode: To place the unit in or out of Manual Mode, quick press the Push Button to toggle the load ON and OFF. When the load
is turned ON manually, the sensor will remain in that state as long as there is motion detected and the time delay has not expired. If the
load is turned OFF manually, the sensor holds the load OFF for as long as motion is detected and then for an additional 5 minutes of no
motion detection. The next time the sensor detects occupancy and the ambient light is lower than the set level, the sensor automatically
turns ON the load.
Test Mode: To place the unit in a 10 minute Test Mode, press the Push Button for about 3 seconds to enter Test Mode, or enable the
Test Mode with the FSIR-100 for the HBP-111. The LED will flash once confirming you are in Test Mode. To exit Test Mode, press and
hold the Push Button for 3 seconds. Walk-test the unit to ensure proper detection.
Service Mode: To place the unit in or exit out of Service Mode, press and hold the Push Button for about 6 seconds. The LED will flash
twice confirming you are in or out of Service Mode. In Service Mode, the LED will always be ON and load status only can be changed by
push button or remote.
Fail On Mode: Pressing and holding the Push Button for about 9 seconds will enable Fail ON. The LED will flash three times confirming
Fail ON is enabled. In this mode, the sensor will turn the connected loads ON upon restoration of power. In the event of a sensing
failure, this mode will ensure power is still available for connected loads. The sensor is set to this mode by default.
Fail Off Mode: Pressing and holding the Push Button for about 12 seconds will enable Fail OFF. The LED will flash four times
confirming Fail OFF is enabled. In this mode, the sensor will keep the connected loads OFF upon restoration of power.
4