DESCRIPTION AND OPERATION
The HBP series occupancy sensors are designed for automatic
lighting control in warehouse high bay applications. All models
contain a passive infrared sensor (PIR). The coverage area
is determined by the selected lens module. The lenses are
interchangeable with any HBP series sensor.
HBP-111
The HBP-111 can be commissioned remotely using the FSIR-100
or with the manual trimpot settings.
HBP-112
The HBP-112 can be commissioned manually by adjusting the
trimpots designated for Time Delay and Light Level settings.
2.76"
(70 mm)
Dimensions
NOTE: Length is 4.95" (125.6m) before retaining clip is removed
and snap-in nipple is collapsed.
Wattstopper
High Bay, Line Voltage, Passive Infrared Occupancy Sensor
Détecteur de mouvement infrarouge passif, Tension de ligne, Grande hauteur
Montaje alto, Voltaje de línea, Sensor de ocupación infrarrojo pasivo
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
4.28"
(108.7 mm)
1.64"
(41.8 mm)
®
SPECIFICATIONS
Voltage ..........120/230 (Single Phase L-N)/277/347 VAC, 50/60 Hz;
Load Requirements:
@120VAC .................................................. 0 - 1000VA, 1/4 HP
@230VAC .............................................................. 0 - 1000 VA
@277VAC .................................................. 0 - 1200VA, 1/4 HP
.......Tungsten, Ballasts, Electronic Ballast, Fluorescent and LED
@347V ........................ 0 - 1500 VA, 1/4 HP; Ballasts and LED
Light Level .......................................................... 1-300 fc (@4000K)
Factory Default .............................................................. Disable
Time Delay Adjustment ......................................1-30 minutes (Remote)
...................................................... 5-30 minutes (Manual Trimpot)
Factory Default ........................................................ 15 minutes
Senstivity ................................................................... Min, Med, Max
Factory Default ................................................................... Max
LENS COVERAGE
The HBP-111/112 occupancy sensors are modular, consisting
of two parts, a Sensor Module and a Lens. When used with the
HBP-L7 lens, the sensors are optimal for mounting heights of
20' to 40'. There is an optional masking accessory for aisle way
applications. Snap it on and rotate to the desired position.
Lens and sensors are indoor rated and are ideal for warehouse
spaces. Avoid placing the sensor where shelving or other
obstructions may block the sensor's line of sight.
Passive Infrared Sensing in Warehouses
Warehouses can have ambient temperature variations that may
affect sensor detection and coverage areas. High temperatures
at the covered area (above 80°F) reduce the detection zone
of the sensor. Consider adding more sensors if the ambient
temperatures are expected to be high. Additionally, high floor
level temperature may require larger movement for detection. In
some cases, sensors mounted above 40' may only detect large
heat signatures such as forklift trucks. See the Best Practices
Guide for Warehouse at www.legrand.us for more information.