Do not install, remove, or reinstall the unit by yourself (customer).
For installation, always contact the dealer or an Authorized service center.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property da-
mage, product failure, and personal injury.
Install the unit securely in a place which can bear the weight of the unit.
- - - - - - - - - - - - - - - - - - - - - - - - - - -
2.1.1 - Minimum room area in the case of refrigerant gas load as per technical data label
(without additional load)
Model
TRIAL 1x3
QUADRI 1x4
PENTA 1x5
TRIAL 1x3
QUADRI 1x4
PENTA 1x5
TRIAL 1x3
QUADRI 1x4
PENTA 1x5
Quantity
of refrigerant gas
(kg)
1,57
2,10
2,40
1,57
2,10
2,40
1,57
2,10
2,40
Height of
installation
(m)
2,2
2,2
2,2
1,8
1,8
1,8
0,6
0,6
0,6
Minimum
room area
(m
2
)
2
3
4
3
5
6
22
38
50
> > > > >
EN - 11
NEXYA S4 E