7. Specifications
MODEL
CAPACITY*
INPUT
Low Line
Transfer
Low Line
Voltage
Comeback
Range
High Line
Transfer
High Line
Comeback
Frequency Range
Phase
Power Factor
THDi
OUTPUT
Output voltage
AC Voltage
Regulation
Frequency Range
(Synchronized
Range)
Frequency Range
Current Crest Ratio
Harmonic Distortion
AC Mode
to Batt.
Transfer
Mode
Time
Inverter to
Bypass
Waveform (Batt.
Mode)
EFFICIENCY
AC Mode
ECO Mode
Battery Mode
BATTERY
Battery Type
Numbers
Recharge Time
Charging Current
Charging Voltage
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
80
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 07 19 AA 59 203 14
E7 One 1000 RT E7 One 1500 RT E7 One 2000 RT
1000VA/1000W
160VAC/140VAC/120VAC/110VAC ± 5 % or 80VAC/70VAC/60VAC/55VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
175VAC/155VAC/135VAC/125VAC ± 5 % or 87VAC/77VAC/67VAC/62VAC ± 5 %
THDU < 1.6% @ input and full linear load condition
200/208/220/230/240VAC or 100/110/115/120/127 VAC
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
≦ 2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
≧ 89% @ full charged battery
≧ 88%
12V/9AH
2
3 hours recover to 95% capacity for internal battery@ 2A charging current
100/110/115/120 /127 VAC models: default 2A, max. 8A
200/208/220/230/240 VAC models: default 2A, max. 12A
27.4 VDC ± 1%
1500VA/1500W
300 VAC ± 5 % or 150 VAC ± 5 %
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz ~ 70 Hz
Single phase with ground
≧ 0.99 @ full load
≦ 5% @ 205-245VAC or 100~130VAC
± 1% (Batt. Mode)
47 ~ 53 Hz or 57 ~ 63 Hz
3:1
Zero
< 4 ms
Pure Sinewave
≧ 96% @ full charged battery
12V/9AH
3
adjustable
adjustable
41.0 VDC ± 1%
E7 One 3000 RT
2000VA/2000W
≧ 91% @ full charged battery
≧ 90%
12V/9AH
4
Default: 2A, Max: 8A
54.7 VDC ± 1%
3000VA / 3000W
12V/9AH
6
adjustable
82.1 VDC ±1%