15: Charger float voltage setting
Interface
16: EPO logic setting
Interface
17: External output isolation transformer connection
Interface
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
72
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 07 19 AA 59 203 14
Setting
Parameter 2: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20 V/cell
to 2.33V/cell. (Default: 2.28V/cell)
Setting
Parameter 2: Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC: Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
Setting
Parameter 2: Allow or disallow external output isolation
transformer connection.
ENA: If selected, it's allowed to connect to an external
output isolation transformer.
DIS: If selected, it's not allowed to connect to external
output isolation transformer. (Default)