04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
06: Bypass enable/disable when UPS is off
Interface
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
68
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 07 19 AA 59 203 14
Setting
Parameter 2: Enable or disable ECO function. You
may choose the following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
Setting
Parameter 2: Set the acceptable high voltage point
and low voltage point for ECO mode by pressing
Down key or Up key.
HLS: High loss voltage in ECO mode in parameter
2.
For 200/208/220/230/240 VAC models, the setting
range in parameter 3 is from +7V to +24V of the
nominal voltage. (Default: +12V)
For 100/110/115/120/127 VAC models, the setting
range in parameter 3 is from +3V to +12V of the
nominal voltage.
(Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting
range in parameter 3 is from -7V to -24V of the
nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting
voltage in parameter 3 is from -3V to -12V of the
nominal voltage.
(Default: -6V)
Setting
Parameter 2: Enable or disable Bypass function. You
may choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)