Mitsubishi Electric CITY MULTI PLFY-P08-P30NBMU-E2 Manuel D'installation page 5

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. Refrigerant pipe and drain pipe
B Refrigerant pipe sizes & Flare nut tightening torque
Liquid pipe
Pipe size
(mm)
torque (N.m)
(inch)
ODø6.35
P08, P12, P15, P18
1/4"
ODø9.52
P24, P30, P36
3/8"
,
Fig. 3-3
Max. 65 ft
5 to 7 ft
Fig. 3-4
7/16
1
1
1
Fig. 3-5
Gas pipe
Tightening
Pipe size
Tightening
(mm)
torque (N.m)
(ft. Ibs)
(inch)
(ft. Ibs)
ODø12.7
14 - 18
49 - 61
10 - 13
35 - 44
1/2"
ODø15.88
34 - 42
68 - 82
25 - 30
49 - 59
5/8"
Refrigerant pipe and
insulating material
Pipe cover (large)
Pipe cover (small)
Refrigerant pipe (gas)
Refrigerant pipe (liquid)
Band
Cross-sectional view of connection
Pipe
Insulating material
Squeeze
Max. 6 inch
(inch)
,
Flare nut O.D.
Liquid pipe
Gas pipe
(mm)
(mm)
(inch)
(inch)
17
26
43/64
1-1/32
22
29
7/8
1-9/64
C Apply refrigerating machine oil over the entire are seat surface.
3.3. Indoor unit (Fig. 3-3)
Heat insulation for refrigerant pipes:
1 Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that
the end of the pipe cover touches the side of the unit.
2 Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure
that the end of the pipe cover touches the side of the unit.
3 Secure both ends of each pipe cover with the enclosed bands. (Attach the
bands 20 mm, 25/32 inch from the ends of the pipe cover.)
• After connecting the refrigerant piping to the indoor unit, be sure to test the pipe
connections for gas leakage with nitrogen gas. (Check that there is no refrigerant
leakage from the refrigerant piping to the indoor unit.)
3.4. Drainage piping work (Fig. 3-4)
• Use VP25 (O.D. ø32 mm, 1-1/4 inch PVC TUBE) for drain piping and provide
1/100 or more downward slope.
• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the gure for piping work.
• Use the included drain hose to change the extraction direction.
1
Correct piping
2
Wrong piping
A
Insulation (9 mm, 23/64 inch or more)
B
Downward slope (1/100 or more)
C
Support metal
K
Air bleeder
L
Raised
M
Odor trap
Grouped piping
D
O. D. ø32 mm, 1-1/4 inch PVC TUBE
E
Make it as large as possible
F
Indoor unit
G
Make the piping size large for grouped piping.
H
Downward slope (1/100 or more)
I
O. D. ø38 mm, 1-1/2 inch PVC TUBE for grouped piping.
(9 mm or more insulation)
J
Up to 850 mm, 33-7/16 inch
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 3-5)
(Fix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32 mm, 1-1/4 inch).
(Fix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 mm, 1-1/4 inch and socket)
4. Check that drain ows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
A
Unit
B
Insulating material
C
Band (large)
D
Drain port (transparent)
E
Insertion margin
F
Matching
G
Drain pipe (O.D. ø32 mm, 1-1/4 inch PVC TUBE)
H
Insulating material (purchased locally)
I
Transparent PVC pipe
J
O.D. ø32 mm, 1-1/4 inch PVC TUBE (Slope 1/100 or more)
K
Band (small)
L
Drain socket
5

Publicité

Chapitres

Table des Matières
loading

Table des Matières