INSTALLATION MANUAL
TERENA - TERENA16
Web Based Access Control

6] THE DOOR CONTROLLER (INTBUSW) AND READERS

The door controller (Ref : INTBUSW)
- An INTBUSW door controller is required for each
reader connected on the RS485 BUS.
- The distance between the central control unit
and the last door controller (INTBUSW) may not
exceed 1000m.
- Pay extreme care not to install wires close to high
power cabling (for example : 230 V AC).
- Recommended wires > 1 twisted pair, SYT1 8/10ths
shielded wire (EIA-485 standard).
The readers (Wiegand format)
- The readers are connected to the door controller
(INTBUSW) using 7 or 8 wires depending
on the technology.

7] SUPPLEMENTARY MODULES

Elevator controller boards (C14D/A)
- The controller is connected to the central control
unit using a 2 wire cable (RS485 BUS >
Recommended cables : 1 twisted pair, SYT1
8/10ths shielded wire (EIA-485 standard).
- 14 "alarm contact" inputs (C14A/E) or 14 "relay contact"
outputs (C14A/S)
- C14D/E and C14A/S address settings are done
using dipswitches (max. 4 per central unit).
C14d/a board address settings
(max. 4 per central unit):
Card 1
Card 2
cdvi.com
10
cdvigroup.com
- The 26, 30 or 44 bit format depends on the type
- The door controller is connected to the central
- The readers must be daisy-chained.
- To secure the installation, do not forget to insert
TERMINAL
Card 3
Card 4
of head used (refer to the attached table
of Wiegand reader formats (factory settings).
control unit using a 2 wire cable (RS485 BUS >
Recommended cables : 1 twisted pair, SYT1
8/10th shielded wire (EIA-485 standard).
a 120 ohm resistor between A and B, on the last
door controller or supplementary module (C14A/E,
C14A/S, C14D/A or C1410S) of the RS485 BUS.
CORRESPONDENCE
C
Common contact relay
1
NO Contact relay 1
2
NO Contact relay 2
3
NO Contact relay 3
4
NO Contact relay 4
5
NO Contact relay 5
6
NO Contact relay 6
7
NO Contact relay 7
8
NO Contact relay 8
9
NO Contact relay 9
10
NO Contact relay 10
11
NO Contact relay 11
12
NO Contact relay 12
13
NO Contact relay 13
14
NO Contact relay 14
M
RS485 Cable shielding
A
"A" of the RS485 BUS
B
"B" of the RS485 BUS
V
12 V DC Power Supply
V
12 V DC Power Supply
EN