Menu - Refco REFMATE Manuel D'utilisation

Masquer les pouces Voir aussi pour REFMATE:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Deutsch
Bedienungsanleitung REFMATE
6.1.3

Menu

Field calibration with
reference pressure
In the navigation, go with
to
and press
.
Use the
tab to carry out the
field calibration of the pressure
sensors.
To start the calibration, enter the
PIN.
The PIN is 0-0-0-9
The device must not be
pressurised at this time!
Press
Connect the device to a system
with a defined pressure.
Pressure range: 10–60 bar,
150-850 psi
The higher the calibration
pressure, the more accurate the
calibration!
Wait until the calibration pressure
corrensponds to the reference
pressure. By clicking
the
respective pressure sensor is
calibrated.
16

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

46880014688129

Table des Matières