1) GENERAL INFORMATION
The SHYRA AC F SL control panel comes with standard factory settings.
Any change must be set by means of the TRIMMER and DIP SWITCH settings.
Its main features are:
- Control of 1 single-phase motor
- Electronic torque control
- Separate inputs for safety devices
- Built-in radio receiver rolling code with transmitter cloning.
The board has a terminal strip of the removable kind to make maintenance or re-
placement easier. It comes with a series of prewired jumpers to make the installer's
job on site easier. The jumpers concern terminals: 70-71, 70-72, 70-74. If the
above-mentioned terminals are being used, remove the relevant jumpers.
TESTING
The SHYRA AC F SL panel controls (checks) the start relays and safety devices
(photocells) before performing each opening and closing cycle.
If there is a malfunction, make sure that the connected devices are working
properly and check the wiring.
2) TECHNICAL SPECIFICATIONS
110-120V 60Hz
(SHYRA AC F SL 120V)
Power supply
220-230V 50/60 Hz
(SHYRA AC F SL 230V)
Fig. F
Panel dimensions
Low voltage/mains insulation > 2MOhm 500V
Operating temperature range -20 / +55°C
Dielectric rigidity
mains/LV 3750V~ for 1 minute
Accessories power supply
4V~ (demand max. 0,2A)
120V~ 40W max
(SHYRA AC F SL 120V)
AUX 0 - Flashing
Contact powered
230V~ 40W max
(SHYRA AC F SL 230V)
Fuses
Fig. C
Built-in Rolling-Code
frequency 433.92MHz
radio-receiver
Setting of parameters and logics TRIMMER + DIP SWITCH
N° of combinations
4 billion
Max. n° of remotes that can
63
be memorized
Pedestrian work time
8 s.
Maximum power
500W
Maximum cycle
S3 33s -1-33s-1x20 pause 36 min.
120s
Maximum work time
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
3) TUBE ARRANGEMENT Fig. A
Install the electrical system referring to the standards in force for electrical systems
CEI 64-8, IEC 364, harmonization document HD 384 and other national standards.
4) TERMINAL BOARD WIRING Fig. C
For the electric diagram and the cross section of the cables refer to the
manual of the actuator.
WARNINGS - When performing wiring and installation, refer to the standards in
force and, whatever the case, apply good practice principles.
Wires carrying different voltages must be kept physically separate from each other,
or they must be suitably insulated with at least 1mm of additional insulation.
Wires must be secured with additional fastening near the terminals, using devices
such as cable clamps.
All connecting cables must be kept far enough away from the dissipater.
WARNING! For connection to the mains power supply, use a multicore cable
with a cross-sectional area of at least 3x1.5mm
the regulations in force.
To connect the motors, use a cable with a cross-sectional area of at least
1.5mm
of the kind provided for by the regulations in force.
2
The cable must be type H05RN-F at least.
5) SAFETY DEVICES
Note: only use receiving safety devices with free changeover contact.
5.1) TESTED DEVICES Fig.G
5.2) CONNECTION OF 1 PAIR OF NON-TESTED PHOTOCELLS FIG. B
WARNING!
The values of the impact force according to EN 12453 are only observed with
the use of safety edges (active) connected to the board.
6) ADJUSTMENT PROCEDURE
- Before turning the unit on, check electrical connections.
- Adjust the mechanical limit switches (where present)
- Carry out an Autoset to set work time
- Set the trimmer
- Set the dip-switch.
WARNING! Incorrect settings can result in damage to property and injury
to people and animals.
WARNING: Check that the force of impact measured at the points provided for
by standard EN 12445 is lower than the value laid down by standard EN 12453.
7) MEMORIZING TRANSMITTERS FIG. D
INSTALLATION MANUAL
.
of the kind provided for by
2
RADIO
-
IMPORTANT NOTE: THE FIRST TRANSMITTER MEMORIZED MUST BE
IDENTIFIED BY ATTACHING THE KEY LABEL (MASTER).
In the event of manual programming, the first transmitter assigns the RECEIVER'S
KEY CODE: this code is required to subsequently clone the radio transmitters.
The Clonix built-in on-board receiver also has a number of important advanced features:
•
Cloning of master transmitter (rolling code).
To use these advanced features, refer to the universal handheld programmer's
instructions and to the general receiver programming guide.
8) ADJUSTING THE AUTOSET FIG. D1/D2
It allows setting the motor work time automatically.
The work times required to carry out opening and closing are measured; the
higher of the 2 measured times is stored and safety time is added to guarantee
complete opening or closing also when the motor performance varies.
WARNING!! The autoset must be carried out only after checking
that the leaf is moving accurately (opening/closing) and the mechanical
stops and limit switches are positioned correctly.
WARNING! During the autoset, the activation of photocells or safety edges
causes the autoset function to fail and be abandoned.
Autoset for motors with limit switches (Fig. D1):
1 - place the leaf at the closing limit switch.
2 - press button S3 for 5 seconds: the SET LED flashes.
3 - press button S3 to start the opening manoeuvre.
4 - wait for the opening limit switch to operate so that the opening manoeuvre
is complete.
5 - press button S3 to start the closing manoeuvre.
6 - wait for the closing limit switch to operate so that the closing manoeuvre is
complete.
7 - If the work time has been stored correctly, the SET LED comes on for 10 seconds.
If autoset fails the SET LED flashes quickly for 10 seconds.
Autoset for motors with no limit switches (Fig. D2):
1 - place the leaf at the gate closure.
2 - press button S3 for 5 seconds: the SET LED flashes.
3 - press button S3 to start the opening manoeuvre.
4 - press button S3 to end the opening manoeuvre.
5 - press button S3 to start the closing manoeuvre.
6 - press button S3 to end the closing manoeuvre.
7 - If the work time has been stored correctly, the SET LED comes on for 10 seconds.
If autoset fails the SET LED flashes quickly for 10 seconds.
9) REVERSING THE OPENING DIRECTION (Fig.E)
KEYS
KEYS
Description
Add Start Key
S1
associates the desired key with the Start command.
Add Pedestrian Key
S2
associates the desired key with the pedestrian command.
S2
Confirms the changes made to parameter settings and operating
>5s
Erase List
S1+S2
WARNING! Erases all memorized transmitters from the
>10s
receiver's memory.
Pressed BRIEFLY, it gives the START command.
S3
HELD DOWN (>5 sec.), it activates the AUTOSET function.
Pressing and holding (>10s) takes the work time back to the default value
23
SHYRA-F -