Precautions regarding overheating of the appliance
This appliance is designed to be mounted on a vertical wall or partition as indicated herein.
It is imperative that there be a gap of 150mm around the charger. The installer must see to it that the
temperature of the air at the input is lower than 65°C in extreme operating conditions.
Measures should also be taken to allow for the discharge of hot air on either side of the charger.
It's strictly forbidden to put any device on or against the charger.
The charger must not be installed near a source of heat; it should be installed in a well-ventilated
area. The charger's air inlets and outlets must not be obstructed.
Be careful hot surface: do not touch the charger during and after its operation (risk of burn).
Precautions regarding dust, seepage and falling water
The charger should be located so as to prevent penetration of damp, liquid, salt and dust, any of
which could cause irreparable damage to the equipment and be potentially hazardous for the user.
The appliance should be installed in a dry and well-ventilated place.
Precautions regarding inflammable materials
The charger should not be used near inflammable materials, liquids or gases.
The batteries can emit explosive gases: please follow the manufacturer's instructions carefully when
installing them.
Nearby the batteries: ventilate the place, do not smoke, do not use any high flame.
Use fuses as defined in this manual.
Other precautions
Never attempt to drill a hole in or to machine the charger's case: this may damage components or
cause metal chips or filings to fall on the charger's board.
Do not do anything that is not explicitly stated in this manual.
1.2.
W

ARRANTY

The manufacturer disclaims the warranty and ENAG waives any liability whatsoever if the installation rules
and instructions for use are not observed.
The warranty is valid for 12 months. It covers parts and labour for equipment returned to the Quimper plant.
Only original parts recognized as being defective will be replaced under the warranty.
Our warranty does not cover:
1. Failure to abide by this manual
2. Any mechanical, electrical or electronic alterations to the appliance
3. Improper use
4. Presence of moisture
5. Failure to comply with AC power-supply tolerances (i.e. overvoltage)
6. Incorrect connections
7. Falls or impacts during transportation, installation or use
8. Repairs carried out by anyone unauthorized by ENAG
9. The maintenance in the energy conversion area made by a non-authorized person by ENAG
(breaking or unsticking of the seal sticker of warranty:"warranty")
10. Connection of any interface not supplied by ENAG
11. The cost of packaging and carriage
12. Apparent or latent damage sustained during shipment and/or handling (any such claims
should be sent to the haulier)
Our warranty on no account provides for any form of compensation. ENAG shall not be held liable for
damage incurred as a result of using the battery charger.