LAYOUT OF THE INSTRUMENT PANEL
fig. 03 Instrument panel
00.31H.79.00010
The Remeha Gas 310 ECO boiler is supplied with
an instrument panel. The Remeha 610 ECO is sup-
plied with an instrument panel on each boiler module.
This instrument panel is provided with an intelligent,
advanced boiler control ('abc
ent menus can be accessed, various values can be read
and settings made. The instrument panel consists of the
following components:
1.
On/off switch.
2.
PC-connection.
3.
Facility for incorporating a rematic
pensator.
A.
Code-display, indication of operating, setting, read-
out, shut-off, test and failure codes.
t-display, indication of temperatures, settings and
B.
shut-off and lock-out codes.
C.
Reset-key, to reset the boiler after a lockout.
m-key, key to select the required mode (mode-key).
D.
s-key, key to select the required program within
E.
the selected mode (step-key).
e-key, key to save the settings (store-key).
F.
G.
[+]-key, to select a higher setting.
H.
[-]-key, to select a lower setting / switch function:
manual override (hand/auto).
The user has a number of setting options, which can
be evoked via the m-key. The desired code (see next
text block) can be chosen by pressing the m-key until
the digit ! (with dot) appears in the code-display. Now
choose the desired code by pressing the s-key. Next,
set the required value in the t-display, using the [+]-
and [-]-keys. Press the e-key to store the new value
(value will flash twice).
To gain access to the service level, the control system
requires an input code.
The boiler control has the following pre-set values:
!
Flow temperature : 90°C
@
Pump run on time : 3 minutes
A
Boiler control
'). Using the keys, differ-
®
weather com-
®
: 31 - modulating on flow
temperature without booster
function.
Settings should only be adjusted after consulting
your installer (or in case of emergency), see section
'Setting mode at user level' in our Technical Information.
Code reports in code-display
1
- only digit or letter; operating mode
!
- digit or letter with dot; setting mode
!
- digit or letter with flashing dot; read-out mode
b
- letter b; shut-off mode (temporary, no boiler failure)
1
- digit flashes;failure mode
Operating mode (x [[)
During operation the code window shows the status
(operation) of the boiler, whereas the t window indi-
cates the measured boiler flow temperature.
Code
Description
Stand-by; no heat demand
0
Vent (pre-ventilation time 12 seconds, post
1
ventilation time 3 seconds)
Ignite
2
The boiler is firing (flame detection)
3
Waiting; checking that there is sufficient air
transport using fan and air pressure differen-
5
tial switch (LDS)
Controls stop (burner off + post ventilation)
6
Run-on time, pump and fan
7
Shutdown mode
b
Gas leakage control
t
10
Remeha
Gas 310/610 ECO